arXivDaily arXiv每日学术速递 周一至周五更新
感恩节,周五至周末无更新,大家顺遂。周一再来吧
arXiv 2203.09190math.OC
收藏

基于OPF松弛法的最优自适应下垂设计

Optimal Adaptive Droop Design via a Modified Relaxation of the OPF

H. Sekhavatmanesh, G. Ferrari-Trecate, S. Mastellone

摘要:

可再生能源(RESs)在配电网络中的渗透率不断增加,带来了将电网电压维持在安全区域内的挑战。在RES逆变器上采用下垂电压调节器是实现这一目标的有效且低成本的解决方案。然而,固定下垂参数或仅针对过压条件对其进行优化,在变化的操作条件下不能提供所需的鲁棒性和最优性。本文提出了一种凸优化方法,用于在线重构PV和QV下垂调节器。其目标是最大限度地减少电力削减,电力损失,电压偏差受电气安全约束。这使得能够在可变条件下以高RES穿透率最佳地操作电网,同时保持电气安全约束(例如,电流和电压限制)。作为第一个贡献,一个混合整数线性模型的下垂特性的开发。根据该模型,下垂调节发电单元被表示为与恒定阻抗负载并联的恒定功率发电机。作为第二个贡献,提出了一种修正的增广松弛最优潮流(MAROPF)制定,以保证在网络中的恒定阻抗负载的存在下,电气安全约束得到尊重。给出了MAROPF解可行的充分条件。这些条件可以被先验地检验,并且对于几个真实的配电网络是有效的。此外,提出了一种迭代方法,以获得一个近似解的MAROPF是接近全局最优的。MAROPF方法的性能和所提出的模型的准确性进行评估标准的34总线和85总线测试网络。

英文摘要:

The ever increasing penetration of Renewable Energy Resources (RESs) in power distribution networks has brought, among others, the challenge of maintaining the grid voltages within the secure region. Employing droop voltage regulators on the RES inverters is an efficient and low cost solution to reach this objective. However, fixing droop parameters or optimizing them only for overvoltage conditions does not provide the required robustness and optimality under changing operating conditions. In this paper, a convex optimization approach is proposed for reconfiguring PV and QV droop regulators during online operation. The objective is to minimize power curtailment, power losses, and voltage deviation subject to electrical security constraints. This enables to optimally operate the grid with high RES penetration under variable conditions while preserving electrical security constraints (e.g., current and voltage limits). As a first contribution, a mixed integer linear model of the droop characteristics is developed. According to this model, a droop regulated generation unit is represented as a constant power generator in parallel with a constant impedance load. As a second contribution, a Modified Augmented Relaxed Optimal Power Flow (MAROPF) formulation is proposed to guarantee that the electrical security constraints are respected in the presence of constant impedance loads in the network. Sufficient conditions for the feasibility of the MAROPF solution are provided. Those conditions can be checked a priori and are valid for several real distribution networks. Furthermore, an iterative approach is proposed to derive an approximate solution to the MAROPF that is close to the global optimal one. The performance of the MAROPF approach and the accuracy of the proposed model are evaluated on standard 34 bus and 85 bus test networks.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑