含分布式电源的配电系统中数据驱动的接地故障定位方法

Data-Driven Ground-Fault Location Method in Distribution Power System With Distributed Generation

Linnaeus University(林奈大学);Uppsala University(乌普萨拉大学)

Mauro Caporuscio, Antoine Dupuis, Welf Löwe

AI总结:

本文提出一种基于离散小波变换和人工神经网络的数据驱动接地故障定位方法,在含分布式电源的配电系统中分别预测故障相、故障支路和故障距离,故障距离预测总相对误差为0.4%。

摘要:

近年来可再生能源在配电层面的渗透率不断提高,引入了多方向潮流,使传统故障定位技术不再适用。为此,需要开发新方法以确保快速、准确的故障定位,从而增强电力系统的可靠性。本文提出了一种面向配电系统的数据驱动接地故障定位方法。在Matlab/Simulink中搭建了一个11母线20 kV电力系统模型,用于模拟接地故障。故障在不同位置和多种系统运行状态下生成。随后利用离散小波变换分析系统变电站处的时域故障三相电压。处理后的数据的统计量最终用于训练人工神经网络(ANN),以建立计算得到的电压特征与故障之间的映射关系。具体而言,三个ANN分别用于预测故障相、故障支路以及故障点距系统变电站的距离。结果表明,该方法展现出良好的潜力,故障距离预测的总相对误差为0.4%。该方法还被应用于系统状态未知的数据集,以测试其鲁棒性。

英文摘要:

The recent increase in renewable energy penetration at the distribution level introduces a multi-directional power flow that outdated traditional fault location techniques. To this extent, the development of new methods is needed to ensure fast and accurate fault localization and, hence, strengthen power system reliability. This paper proposes a data-driven ground fault location method for the power distribution system. An 11-bus 20 kV power system is modeled in Matlab/Simulink to simulate ground faults. The faults are generated at different locations and under various system operational states. Time-domain faulted three-phase voltages at the system substation are then analyzed with discrete wavelet transform. Statistical quantities of the processed data are eventually used to train an Artificial Neural Network (ANN) to find a mapping between computed voltage features and faults. Specifically, three ANNs allow the prediction of faulted phase, faulted branch, and fault distance from the system substation separately. According to the results, the method shows good potential, with a total relative error of 0,4% for fault distance prediction. The method is applied to datasets with unknown system states to test robustness.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑