协调控制与下垂控制PV逆变器的相互影响

Interaction Between Coordinated and Droop Control PV Inverters

Peter Lusis, Lachlan L. H. Andrew, Ariel Liebman, Guido Tack

摘要:

与没有电网支持功能的逆变器相比,自主下垂控制PV逆变器具有改进的电压调节,但随着太阳能光伏(PV)装置数量的增加,将需要更灵活的控制技术。本文研究了三种逆变器未来部署方案,包括下垂控制逆变器、非出口逆变器和协调逆变器控制(CIC)。通过仿真逆变器在两个低压电网上的运行,研究了电网运行和各种逆变器控制方法之间的相互作用。考虑30%的光伏渗透率为基础的情况下,我们证明,协调逆变器可以减轻过电压和电压波动所造成的跳闸的无源逆变器在85%的光伏位置的情况下,至少有尽可能多的协调无源逆变器部署在114节点的测试馈线。然而,这一比率降低到37%,IEEE 906节点网络表明,当无源逆变器的建立达到一定阈值时,协调逆变器控制的部署可能无法逆转无源逆变器相关的电压扰动。来自协调逆变器的聚合PV输出也可用于提供电网支持服务。当低压网络接近电压上限运行时,在调节请求之后来自协调逆变器的功率输出的变化可以被无源逆变器部分抵消。考虑到相同数量的被动和协调逆变器,本文表明,对于每个单位的协调逆变器提供的下调请求,被动逆变器输出可能会增加多达0.2个单位,并减少多达0.45个单位,在协调逆变器的上调。

英文摘要:

Autonomous droop control PV inverters have improved voltage regulation compared to the inverters without grid support functions, but more flexible control techniques will be required as the number of solar photovoltaic (PV) installations increases. This paper studies three inverter future deployment scenarios with droop control inverters, non-exporting inverters, and coordinated inverter control (CIC). The network operation and the interaction between various inverter control methods are studied by simulating inverter operation on two low-voltage networks. Considering 30% PV penetration as the base case, we demonstrate that coordinated inverters can mitigate overvoltages and voltage fluctuations caused by the tripping of passive inverters in 85% of PV location cases when at least as many coordinated as passive inverters are deployed on the 114-node test feeder. However, this rate reduced to 37% with the IEEE 906-node network demonstrating that the deployment of coordinated inverter control may not be able to reverse passive inverter-related voltage disturbances when the build-up of passive inverters has reached a certain threshold. The aggregated PV output from coordinated inverters can be also used to provide grid support services. When the low-voltage networks operate close to the upper voltage limits, the change in the power output from coordinated inverters following a regulation request may be partially offset by passive inverters. Considering an equal number of passive and coordinated inverters, this paper shows that for each unit of the down-regulation request delivered by coordinated inverters, passive inverter output may increase by up to 0.2 units and decrease by up to 0.45 units during coordinated inverter up-regulation.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑