The proliferation of inverter-based generation and advanced sensing, controls, and communication infrastructure have facilitated the accelerated deployment of microgrids. A coordinated network of microgrids can maintain reliable power delivery to critical facilities during extreme events. Low inertia offered by the power electronics interfaced energy resources however, can present significant challenges to ensuring stable operation of the microgrids. In this work, distributed small-signal stability conditions for inverter-based microgrids are developed that involve the droop controller parameters and the network parameters such as line impedances, loads, etc. The distributed closed-form parametric stability conditions derived in this paper can be verified in a computationally efficient manner, facilitating the reliable design and operations of networks of microgrids. Dynamic phasor models have been used to capture the effects of electromagnetic transients. Numerical results are presented, along with PSCAD simulations, to validate the analytical stability conditions. Effects of design choices, such as the conductor types, and inverter sizes, on the small-signal stability of inverter-based microgrids are investigated to identify interpretable stable or unstable region estimates.
An islanded microgrid supplied by multiple distributed energy resources (DERs) often employs droop-control mechanisms for power sharing. Because microgrids do not include inertial elements, and low pass filtering of noisy measurements introduces lags in control, droop-like controllers may pose significant stability concerns. This paper aims to understand the effects of droop-control on the small-signal stability and transient response of the microgrid. Towards this goal, we present a compendium of results on the small-signal stability of droop-controlled inverter-based microgrids with heteroge…
In this paper, we investigate the stability properties of inverter-based microgrids by establishing the possible presence of the so-called critical clusters - groups of inverters with their control settings being close to the stability boundary. For this, we consider the spectrum of the weighted admittance matrix of the network and show that its distinct eigenvalues correspond to inverter clusters, whose structure can be revealed by the corresponding eigenvector. We show that the maximum eigenvalue of the weighted admittance matrix corresponds to the cluster, closest to stability boundary. We …
This paper presents a method for controlling the voltage of inverter-based Microgrids by proposing a new scale-free distributed cooperative controller. The communication network is modeled by a general time-varying graph which enhances the resilience of the proposed protocol against communication link failure, data packet loss, and fast plug and play operation in the presence of arbitrarily communication delays. The proposed scale-free distributed cooperative controller is independent of any information about the communication system and the size of the network (i.e., the number of distributed…
Superimposed sequence quantities have been relied on for years to provide pure fault components for various applications in protection schemes. In more recent times, they have been employed in various solutions to the challenges introduced by integration of distributed generation in distribution systems. To improve the overall reliability of protection schemes deployed in such active distribution networks, this paper evaluates a new approach for detecting unbalanced faults using negative sequence quantities. A proposed superimposed negative sequence admittance element is validated using simula…
Inverter-interfaced microgrids results in challenges when designing protection systems. Traditional time-overcurrent, admittance, and differential protection methods are unsuitable on account of lack of fault current, excessively short lines, or a prohibitive number of protective devices needing to be installed. Current practice is to force all inverters to shut down during fault conditions, weakening resilience and reducing reliability. Dynamic state estimation (DSE), which has been explored for both line protection and load bus protection before, is a potential solution to these challenges t…
A new method for stability assessment of inverter-based microgrids is presented in this paper. It leverages the notion of critical clusters -- a localized group of inverters with parameters having the highest impact on the system stability. The spectrum of the weighted network admittance matrix is proposed to decompose a system into clusters and rank them based on their distances from the stability boundary. We show that each distinct eigenvalue of this matrix is associated with one cluster, and its eigenvectors reveal a set of inverters that participate most in the corresponding cluster. The …
This paper developed a novel control approach for the sparse and safe frequency regulation for inverter intensive microgrids (MGs). In the scenario, the inverters and external grids are expected to reach a synchronized desired frequency under regulations. To this end, the active power set-point acting as a control from a high-level controller is designed while considering two important performance metrics "sparsity" and "safety", which are to reduce the information exchange between controllers and ensure that the frequency keeps in safety regions during the whole operation process. Our propose…
A new method for the stability assessment of inverter-based microgrids is presented in this paper. Directly determining stability boundaries by searching the multidimensional space of inverters' droop gains is a computationally prohibitive task. Instead, we build a certified stability region by utilizing a generalized Laplacian matrix eigenvalues, which are a measure of proximity to stability boundary. We establish an upper threshold for the eigenvalues that determines the stability boundary of the entire system and demonstrate that this value depends only on the network's R/X ratio but does n…
The rapid increase of distributed energy resources has led to the widespread deployment of microgrids. These flexible and efficient local energy grids are able to operate in both grid-connected mode and islanded mode; they are interfaced to the main power system by a fast semiconductor switch and commonly make use of inverter-interfaced generation. This paper focuses on inverter interfaced microgrids, which present a challenge for protection as they do not provide the high short-circuit current necessary for conventional time-overcurrent protection. The application of admittance relaying for t…
Unbalanced and nonlinear loads connected to microgrids (MG) with local distributed energy resources (DERs) are two of the leading causes of power quality problems. Nonlinearloads introduce voltage and current harmonics, and single-phase loads can cause voltage and current imbalances in a three-phase network. This paper presents a hierarchical control scheme for voltage-controlled photovoltaic (PV) inverters with unbalanced and nonlinear loads in micro-grids. The hierarchical control consists of primary control and voltage compensation control(VCC) and a DC voltage regulator (VR). The primary c…
This paper proposes a new distributed consensus-based control method for voltage and frequency control of fully inverter-based islanded microgrids (MGs). The proposed method includes the active power sharing in voltage control to improve the reactive power sharing accuracy and thus generalizes some existing secondary frequency and voltage control methods. Firstly, frequency is regulated by distributed secondary frequency control. Secondly, voltage is regulated by distributed average voltage control and decentralized individual voltage control. It offers a tunable trade-off between voltage regu…
Microgrids are increasingly recognized as a key technology for the integration of distributed energy resources into the power network, allowing local clusters of load and distributed energy resources to operate autonomously. However, microgrid operation brings new challenges, especially in islanded operation as frequency and voltage control are no longer provided by large rotating machines. Instead, the power converters in the microgrid must coordinate to regulate the frequency and voltage and ensure stability. We consider the problem of designing controllers to achieve these objectives. Using…
In this paper, the short-term operation problem for a multiple energy carrier hybrid AC/DC microgrid is discussed. The hybrid microgrid consists of AC and DC parts, which are connected by means of inverters as well as natural gas network. The microgrid includes photovoltaic (PV) unit, wind turbine (WT), battery storage unit and gas-fired microturbines. A mixed integer linear programming is formed to minimize the overall cost of the microgrid including cost of natural gas supply, the value of lost load and battery degradation cost. The presented case study explored the importance of inverter ch…
This paper presents a novel grid-forming voltage control strategy for a battery energy storage system to maintain balanced three-phase output voltages when serving unbalanced loads. A stationary reference frame ($αβ$) based control scheme is proposed to regulate positive-sequence and negative-sequence voltages. Compared with the conventional rotating reference frame ($dq$) based control scheme, the proposed scheme shows better dynamic performance. Then, we analyze the system zero-sequence network and propose adding a grounding transformer to the Y/Yg connected output transformer to further red…
Modern safety-critical energy infrastructures are increasingly operated in a hierarchical and modular control framework which allows for limited data exchange between the modules. In this context, it is important for each module to synthesize and communicate constraints on the values of exchanged information in order to assure system-wide safety. To ensure transient safety in inverter-based microgrids, we develop a set invariance-based distributed safety verification algorithm for each inverter module. Applying Nagumo's invariance condition, we construct a robust polynomial optimization proble…
The electric grid modernization effort relies on the extensive deployment of microgrid (MG) systems. MGs integrate renewable resources and energy storage systems, allowing to generate economic and zero-carbon footprint electricity, deliver sustainable energy to communities using local energy resources, and enhance grid resilience. MGs as cyberphysical systems include interconnected devices that measure, control, and actuate energy resources and loads. For optimal operation, cyberphysical MGs regulate the onsite energy generation through support functions enabled by smart inverters. Smart inver…
A Communication-Free Master-Slave Microgrid with Power Sharing
Johann Bernoulli Institute for Mathematics and Computer Science, University of Groningen(格罗宁根大学约翰·伯努利数学与计算机科学研究所);Engineering and Technology Institute, University of Groningen(格罗宁根大学工程与技术研究所)
The connection of single-phase microgrids (MG) and loads to three-phase MGs creates power quality problems such as unbalanced voltage and voltage rise at the point of common coupling (PCC) of the MGs. In this paper, a modified reverse droop control (MRDC) scheme in the Energy Storage System (ESS) is proposed to improve the three-phase PCC voltage quality in multi-microgrids (MMG). The MRDC consists of a reactive power compensator (RPC) and a voltage compensator. The controller regulates the reactive power and voltage unbalance of the MMG by using the reactive power produced by the ESS. The eff…
In a purely inverter-based microgrid, both grid-forming (GFM) and grid-following (GFL) inverters will have a crucial role to play in frequency/voltage regulation and maintaining power sharing through their grid support capabilities. Consequently, the coordination between these two technologies becomes increasingly important for optimal system performance. However, the existing work does not consider GFL's potential to participate in a secondary control in coordination with GFM, thus not able to utilize the full capability of inverter resources. In this paper, we show that it is possible to ful…
The integration of single-phase distributed generations (DG) and unbalanced loads to three-phase DGs brings challenges to the operating system of the microgrids (MGs). These challenges include unbalanced voltage and unequal power flow at the point of common coupling (PCC) of the MGs. The aim of this paper is to develop an Energy Storage System (ESS) with multi-function control for islanded multi-microgrids (MMG) consisting of single and three PV-DGs to enhance its power quality and power-sharing of the MMGs. The proposed multi-function control consists of a reactive power compensation (RPC), a…
Advanced microgrids consisting of distributed energy resources interfaced with multi-inverter systems are becoming more common. Consequently, the effectiveness of voltage and frequency regulation in microgrids using conventional droop-based methodologies is challenged by uncertainty in the sizeand schedule of loads. This article proposes an isochronous architecture of parallel inverters with only voltage-active power droop (VP-D) control for improving active power sharing as well as plug-and-play of multi-inverter based distributed energyresources (DERs). In spite of not employing explicit con…
Grid-forming inverter-based autonomous microgrids present new operational challenges as the stabilizing rotational inertia of synchronous machines is absent. The design of efficient control policies for grid-forming inverters is, however, a non-trivial problem where multiple performance objectives need to be satisfied, including voltage/frequency regulation, current limiting capabilities, as well as active power sharing and a scalable operation. We propose in this paper a novel control architecture for frequency and voltage control which allows current limitation via an inner loop, active powe…
Photovoltaic (PV) smart inverters can improve the voltage profile of distribution networks. A multi-objective optimization framework for coordination of reactive power injection of smart inverters and tap operations of on-load tap changers (OLTCs) for multi-phase unbalanced distribution systems is proposed. The optimization objective is to minimize voltage deviations and the number of tap operations simultaneously. A novel linearization method is proposed to linearize power flow equations and to convexify the problem, which guarantees convergence of the optimization and less computation costs.…
As multi-microgrids become readily available, some limited models have been proposed that study operational and power quality constraints with local energy markets independently. This paper proposes a convex optimization model of an energy management system with operational and power quality constraints and interactions in a Local Energy Market (LEM) for unbalanced microgrids (MGs). The LEM consists of a pre-dispatch step and an energy transactions step (ETS). The ETS combines the MGs' objectives while considering two strategies: minimize the cost of buyers or maximize the revenue of sellers. …
The proliferation of distributed energy resources (DERs) im-poses new challenges to distribution system operation, e.g., power quality issues. To overcome these challenges and enhance system operation, it is critical to effectively utilize all available resources and accurately characterize unbalanced distribution networks in operational tools. This paper proposes a convex second-order-cone programming (SOCP)-based AC optimal power flow (ACOPF) model for three-phase unbalanced distribution net-works, including smart inverters and Volt-VAr controller (VVC) devices. Reactive power-voltage (Q-V) …
Fully Distributed Secondary Voltage Control in Inverter-Based Microgrids
Lane Department of Computer Science and Electrical Engineering, West Virginia University(西弗吉尼亚大学计算机科学与电气工程学院);Advanced Power & Electricity Research Group (APERC)(先进电力与能源研究小组 (APERC));Wireless Sensor Actuator Networks (WSAN) Research Group(无线传感器执行器网络研究小组)
This research addresses distributed proportional power sharing of inverter-based Distributed Generators (DGs) in microgrids under variations in maximum power capacity of DGs. A microgrid can include renewable energy resources such as wind turbines, solar panels, fuel cells, etc. The intermittent nature of such energy resources causes variations in their maximum power capacities. Since DGs in microgrids can be regarded as Multi-Agent-Systems (MASs), a consensus algorithm is designed to have the DGs generate their output power in proportion to their maximum capacities under capacity fluctuations…
A survey on modeling of microgrids - from fundamental physics to phasors and voltage sources
University of Leeds(利兹大学);Tufts University(塔夫茨大学);Siemens AG(西门子股份公司);Technische Universität Berlin(柏林工业大学);Max-Planck-Institut für Dynamik komplexer technischer Systeme(马克斯·普朗克复杂技术系统动力学研究所)