一种改进的两级并网PV系统:分数阶控制器

An Advanced Two-Stage Grid Connected PV System: A Fractional-Order Controller

Shah Fahad, Nasim Ullah, Ali Jafer Mahdi, Asier Ibeas, Arman Goudarzi

摘要:

提出了一种基于分数阶控制器的光伏并网发电系统控制器。单相两级并网光伏发电机(PVG)被用来测试FO控制器的性能。所提出的控制器的主要目标是:(1)调节PVG的输出电压在一个点,其中最大功率被提请。(2)恒定直流链路电压控制。(3)逆变器输出端的功率因数控制(PFC),具有低总谐波失真(THD)。为了解决第一个问题,一个非线性控制方法称为分数阶反推控制(FOBSC)被用来调节PVG的输出电压。使用称为扰动和观察(P & O)的最大功率点跟踪(MPPT)技术来生成适合于跟踪PVG的最大功率生成的参考电压。产生的基准电压用于使用FOBSC调节PVG的输出电压。直流侧电压波动问题采用基于FO的PI控制器来解决。最后一个目标是实现使用FOBSC,以获得最大的电网功率因数。利用李雅普诺夫候选函数验证了系统的稳定性。为了测试所提出的控制器的性能,它是比较传统的整数阶(IO)控制器。结果表明,系统的THD和效率有显着改善。与IO控制器相比,该控制器在PVG发电容量的100%、80%和70%时,THD分别降低了0.94%、1.43%和1.86%。注意到在FO控制器的情况下,对于系统的100%、80%和70%的动态功率的系统的总效率更好。

英文摘要:

A fractional-order (FO) based controller for a grid-connected PV system is presented in this paper. A single phase two-stage grid-connected photovoltaic generator (PVG) is used to test the performance of the FO controller. The main objectives of the proposed controller are: (1) To regulate the output voltage of PVG at a point where the maximum power is drawn. (2) Constant DC-link voltage control. (3) Power factor control (PFC) at the inverter output with low total harmonic distortion (THD). To solve the first problem, a non-linear control method known as fractional-order back-stepping control (FOBSC) is used to regulate the output voltage of PVG. A maximum power point tracking (MPPT) technique known as perturb and observe (P & O) is used to generate a reference voltage which is suitable for tracking the maximum power generation of PVG. The generated reference is used to regulate the output voltage of PVG using FOBSC. The DC-link voltage fluctuation issue is tackled using FO based PI controller. The last objective is achieved using FOBSC to obtain maximum power factor of the grid. Lyapunov candidate function is used to verify the stability of the system. To test the performance of the proposed controller, it is compared to conventionally known Integer-order (IO) controller. Results have shown a significant improvement in THD and efficiency of the system. The proposed controller offers 0.94%, 1.43% and 1.86% lower THD in comparison with IO controller at 100%, 80% and 70% of the power generation capacity of PVG, respectively. The overall efficiency of the system for 100%, 80%, and 70% of the dynamic powers of the system is noticed to be better in case of FO controller.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑