用于配电网无功潮流优化的在线反馈优化控制器的部署

Deployment of an Online Feedback Optimization Controller for Reactive Power Flow Optimization in a Distribution Grid

Lukas Ortmann, Christian Rubin, Alessandro Scozzafava, Janick Lehmann, Saverio Bolognani, Florian Dörfler

AI总结:

本文在实际配电网中部署了基于在线反馈优化(OFO)的无功潮流控制器,利用现有逆变器在满足电压约束的同时优化变电站无功潮流,并验证其达到TRL 7级。

摘要:

优化是电网运行的重要组成部分,近年来在线优化方法日益受到关注。其中一种方法是在线反馈优化(Online Feedback Optimization,OFO),它利用来自电网的测量值作为反馈,迭代地改变控制输入,直到它们收敛到优化问题的解。此类算法已应用于许多电力系统问题,并在实验室环境中进行了实验验证。本文使用现成的硬件和软件,在实际配电网中实现了一个OFO控制器,用于7×24小时运行。所提出的控制策略在满足电压约束的同时优化变电站的无功潮流。作为(子)输电系统运营商(TSO)与配电系统运营商(DSO)之间现有协调方案的一部分,该策略可带来经济回报,同时通过调节馈线上的电压来虚拟增强电网,从而允许更高水平的分布式发电/用电。我们介绍了如何对配电网进行改造,以便能够利用现有的逆变器,分析了控制器与既有基础设施的交互作用,并研究了其整体控制行为。最后,我们展示了OFO控制器在实际运行环境中的成功部署,这对应于技术就绪水平(Technology Readiness Level,TRL)7级。

英文摘要:

Optimization is an essential part of power grid operation and lately, Online Optimization methods have gained traction. One such method is Online Feedback Optimization (OFO) which uses measurements from the grid as feedback to iteratively change the control inputs until they converge to the solution of the optimization problem. Such algorithms have been applied to many power system problems and experimentally validated in lab setups. This paper implements an OFO controller in a real distribution grid for 24/7 operation using off-the-shelf hardware and software. The proposed control strategy optimizes the reactive power flow at the substation while satisfying voltage constraints. As part of an existing coordination scheme between (sub)transmission grid operator (TSO) and distribution grid operator (DSO), this comes with a financial reward and simultaneously it virtually reinforces the grid by regulating the voltage on the feeder and therefore allowing higher levels of distributed generation/consumption. We present how a distribution grid is retrofitted such that we can use existing inverters, we analyze the controller's interaction with legacy infrastructure, and investigate its overall control behavior. Finally, we demonstrate the successful deployment of an OFO controller in an operational environment which corresponds to Technology Readiness Level (TRL) 7.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑