抑制基于逆变器资源(IBR)引发的振荡的STATCOM鲁棒自适应控制

Robust Adaptive Control of STATCOMs to Mitigate Inverter-Based-Resource (IBR)-Induced Oscillations

Hui Yuan, Linbin Huang, Huisheng Gao, Jikui Xing, Di Zheng, Ruisheng Diao

AI总结:

本文提出一种从电网强度角度揭示STATCOMs对多IBR系统振荡影响机制的新方法,识别关键运行条件并简化稳定性分析,据此设计了确保系统在变化条件下鲁棒稳定的STATCOMs自适应控制参数,经改进IEEE39节点系统验证有效。

摘要:

基于逆变器资源(IBRs)与电网之间的相互作用可能引发小信号稳定性问题,在低短路容量电网中尤为明显。此外,在多IBR系统中接入静止同步补偿器(STATCOMs)以提供电压支持,可能会进一步恶化小信号稳定性。然而,由于系统动态复杂且运行条件多变,全面理解STATCOMs对IBR引发振荡问题的影响机制,以及设计最优的STATCOMs控制策略以抑制多IBR系统中的这些振荡问题,仍然具有挑战性。为应对这些挑战,本文提出了一种新方法,从电网强度的角度揭示STATCOMs如何影响多IBR系统中的IBR引发振荡问题,并能够考虑变化的运行条件。基于该方法,识别出了系统最容易失稳的关键运行条件。此外,我们证明了在关键运行条件下,含STATCOMs的多IBR系统的小信号稳定性问题可以简化为多个子系统的问题,从而避免了对多种运行条件进行详细系统模型的穷举研究。在此基础上,提出了一种STATCOMs的自适应控制参数设计方法,以确保系统在变化的运行条件下的鲁棒稳定性。所提方法通过改进的IEEE39节点测试系统进行了验证。

英文摘要:

The interaction among inverter-based resources (IBRs) and power network may cause small-signal stability issues, especially in low short-circuit-level grids. Besides, integrating static synchronous compensators (STATCOMs) in a multi-IBR system for voltage support can deteriorate small-signal stability. However, it is still challenging to fully understand the impact mechanism of STATCOMs on IBR-induced oscillation issues and to design optimal STATCOMs' control for dampening these oscillation issues in a multi-IBR system due to complex system dynamics and varying operating conditions. To tackle these challenges, this paper proposes a novel method to reveal how STATCOMs influence IBR-induced oscillation issues in a multi-IBR system from the viewpoint of grid strength, which can consider varying operating conditions. Based on this proposed method, critical operating conditions are identified, wherein the system tends to be most unstable. Moreover, we demonstrate that robust small-signal stability issues of the multi-IBR system with STATCOMs can be simplified as that of multiple subsystems under critical operating conditions, which avoids exhaustive studies on many operating conditions with detailed system models. On this basis, an adaptive control-parameter design method is proposed for STATCOMs to ensure system robust stability under varying operating conditions. The proposed methods are validated by a modified IEEE39-node test system.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑