arXivDaily arXiv每日学术速递 周一至周五更新
arXiv周末暂无论文更新,休息一下吧,周末愉快~~
arXiv 2203.05670physics.flu-dyn
收藏

CFD模拟浮力驱动通风在三层办公楼中的全尺寸验证

Full-scale validation of CFD simulations of buoyancy-driven ventilation in a three-story office building

Chen Chen, Catherine Gorlé

摘要:

计算流体动力学(CFD)经常用于支持自然通风建筑的设计;然而,应彻底评估模型的准确性,最好通过全尺寸测量进行验证。本研究的目的是(1)验证瞬态计算流体力学模拟与不确定性量化(UQ)浮力驱动的自然通风对全尺寸实验中的运行中庭建筑,(2)量化的热边界条件的计算流体力学结果的敏感性。UQ和敏感性分析考虑了温度的初始和边界条件的不确定性。考虑到每层的体积平均空气温度,预测和测量吻合良好,误差小于0.3 °C。当考虑每层楼较小区域的平均温度时,可以观察到两种趋势。首先,在不邻近窗户的区域,计算流体动力学和测量之间的差异可以通过边界条件和测量的不确定性来解释。其次,在窗口附近区域,由于窗口下游流入射流的振荡以及CFD模型中的几何简化,观察到更高的差异。灵敏度分析表明,热质量表面温度和室外温度的边界条件对室内空气温度的预测具有主导作用,其相对重要性随靠近窗户的程度而变化。

英文摘要:

Computational fluid dynamics (CFD) is frequently used to support the design of naturally ventilated buildings; however, the model accuracy should be thoroughly assessed, ideally through validation with full-scale measurements. The present study aims to (1) validate transient CFD simulations with uncertainty quantification (UQ) for buoyancy-driven natural ventilation against full-scale experiments in an operational atrium building, and (2) quantify the sensitivity of the CFD results to the thermal boundary conditions. The UQ and sensitivity analysis consider uncertainties in the initial and boundary conditions for the temperatures. Considering the volume-averaged air temperature on each floor, the predictions and measurements agree well with discrepancies less than 0.3 °C. When considering the temperature averaged over smaller zones on each floor, two trends can be observed. First, in zones not adjacent to windows, the discrepancies between the CFD and measurements can be explained by uncertainty in the boundary conditions and the measurements. Second, in zones adjacent to windows, higher discrepancies are observed due to oscillations in the inflow jets just downstream of the windows, and due to geometrical simplifications in the CFD model. The sensitivity analysis demonstrates that the boundary conditions for the thermal mass surface temperature and the outdoor temperature have a dominant effect on the indoor air temperature predictions, with their relative importance varying as function of proximity to the windows.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑