arXiv 2602.00519physics.flu-dyn
收藏

工业通风系统中变频驱动风扇系统滤网堵塞惩罚的数字孪生评估

Digital Twin Assessment of Filter Clogging Penalties in VFD-Driven Industrial Fan Systems

Polar Dynamix

Wichai Pattanapol, Adam Gill

AI总结:

本研究通过数字孪生技术量化工业通风系统中滤网堵塞导致的能源惩罚,揭示了变频驱动器在极端堵塞条件下的性能限制及优化维护策略的重要性。

摘要:

在配备变频驱动器(VFDs)的工业通风系统中,滤网堵塞的气动影响常常被自动增加风扇速度以维持空气流量设定点所掩盖。虽然这有助于过程稳定性,但这种控制策略会在能源管理方面造成一个

英文摘要:

Industrial ventilation systems equipped with variable-frequency drives (VFDs) often mask the aerodynamic impact of filter clogging by automatically increasing fan speed to maintain airflow setpoints. While effective for process stability, this control strategy creates a "blind spot" in energy management, leading to unmonitored power spikes. This study applies a rapid digital twin workflow to quantify these hidden energy penalties in a standard 50 kW draw-through fan room. Using a specialized computational fluid dynamics (CFD) solver (AirSketcher), the facility was modeled under "Clean Filter" (baseline) and "Dirty Filter" (clogged) scenarios. The physics engine was first validated against wind tunnel experimental data, confirming high agreement with the theoretical inertial pressure-drop law ($ΔP \propto U^2$). In the industrial case study, results indicate that severe clogging (modeled via a 50% effective porosity reduction) can push the fan system beyond its available pressure head or speed limits, forcing the VFD into a saturation regime. Under these conditions, effective airflow collapses by over 50% (3,806 CFM to 1,831 CFM) despite increased fan effort. The associated energy analysis predicts an annual energy penalty of 8,818 kWh ($1,058/yr). This study demonstrates how a physics-based simulation provides a defensible, ROI-driven metric for optimizing filter maintenance cycles. Keywords - industrial ventilation; digital twin; VFD optimization; filter maintenance; CFD; energy efficiency

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑