均匀分布的地板浮力源可在房间内引起显著的空间不均匀性

Uniformly distributed floor sources of buoyancy can give rise to significant spatial inhomogeneities within rooms

Carolanne V. M. Vouriot, Thomas D. Higton, P. F. Linden, Graham O. Hughes, Maarten van Reeuwijk, Henry C. Burridge

AI总结:

本研究通过实验和CFD模拟发现,均匀加热地板驱动的置换通风中,温差的水平变化虽对整体通风量预测影响小,但对室内流动模式至关重要,尤其在对端通风时上部会形成死区,影响污染物暴露。

摘要:

置换通风是指冷空气通过低位通风口进入房间,暖空气通过高位通风口排出的通风方式,其特征是由较高的室内温度引起的垂直压力梯度。模型通常假设温差的水平变化较小,因此不重要。小规模实验室实验和计算流体动力学被用于研究由均匀加热地板驱动的这些流动。这些实验和模拟表明,在预测整体通风量时,温差的水平变化可以忽略;然而,它们也证明这些水平变化可能很显著,并在建立房间内的流动模式中起关键作用——这使得低位和高位通风口的水平位置(相对于彼此)变得重要。我们考虑两种情况:单端式(入口和出口在房间的同一端)和对端式。在两种情况下,通风流量相同。然而,在对端式情况下,房间上部形成一个死区,导致显著的水平变化。我们通过检查流线模式和房间内空气年龄来研究这个死区的形成。我们讨论了对居住者暴露于污染物和空气传播疾病的影响。

英文摘要:

Displacement ventilation, where cool external air enters a room through low-level vents and warmer air leaves through high-level vents, is characterised by vertical gradients in pressure arising from the warmer indoor temperatures. Models usually assume that horizontal variations of temperature difference are small in comparison and are, therefore, unimportant. Small-scale laboratory experiments and computational fluid dynamics were used to examine these flows, driven by a uniformly heated floor. These experiments and simulations show that the horizontal variations of temperature difference can be neglected for predictions of the bulk ventilation rate; however, they also evidence that these horizontal variations can be significant and play a critical role in establishing the pattern of flow within the room -- this renders the horizontal position of the low- and high-level vents (relative to one another) important. We consider two cases: single-ended (where inlet and outlet are at the same end of the room) and opposite-ended. In both cases the ventilation flow rate is the same. However, in the opposite-ended case a dead zone is established in the upper part of the room which results in significant horizontal variations. We consider the formation of this dead zone by examining the streamline patterns and the age of air within the room. We discuss the implications for occupant exposure to pollutants and airborne disease.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑