The energy transition towards high shares of renewable energy will affect the stability of electricity grids in many ways. Here, we aim to study its impact on propagation of disturbances by solving nonlinear swing equations describing coupled rotating masses of synchronous generators and motors on different grid topologies. We consider a tree, a square grid and as a real grid topology, the German transmission grid. We identify ranges of parameters with different transient dynamics: the disturbance decays exponentially in time, superimposed by oscillations with the fast decay rate of a single node, or with a smaller decay rate without oscillations. Most remarkably, as the grid inertia is lowered, nodes may become correlated, slowing down the propagation from ballistic to diffusive motion, decaying with a power law in time. Applying linear response theory, we show that tree grids have a spectral gap leading to exponential relaxation as protected by topology and independent on grid size. Meshed grids are found to have a spectral gap which decreases with increasing grid size, leading to slow power law relaxation and collective diffusive propagation of disturbances. We conclude by discussing consequences if no measures are undertaken to preserve the grid inertia in the energy transition.
The European Electricity Grid System and Winter Peak Load Stress: For how long can the european grid system survive the ever increasing demand during cold winter days?
Features of a fully renewable US electricity system: Optimized mixes of wind and solar PV and transmission grid extensions
根据32年的天气数据(时间分辨率为1小时,空间分辨率为40x40 km $^2$)计算了整个美国邻近地区的风能和太阳能光伏发电数据,并假设全国各地的风能和太阳能光伏发电容量分布是基于场地适用性的随机分布。这些数据用于研究完全可再生的电力系统,主要依靠风能和太阳能光伏发电。我们发现,由于美国夏季负荷高峰,风能和太阳能光伏的季节性最佳组合约为80%的太阳能光伏份额。通过选择这种组合,长期存储需求可以减少一半以上相比,风只混合。由于太阳能光伏发电的夜间间隙,每日最佳组合约为80%的风能份额。选择这种组合而不是太阳能只能减少约50%的备用能源需求。此外,我们计算了FERC(联邦能源管理委员会)水平的LCOE(电力平准化成本)的变化,因为它们的资源质量和波动模式不同。由于地区条件的不同,LCOE的差异高达35%,LCOE的最佳组合在很大程度上取决于资源质量。基于一种新的最小成本优化方法,构建了一个FERC区域之间的传输网络增强,以传输跨FERC边界的太阳能和风能的高穿透率。