arXiv 2605.01173eess.SYcs.SY
收藏

限制人工智能数据中心对电网同步发电机热力涡轮机发电机疲劳寿命的影响:一种频域方法

Limiting the Impact of AI Data Centers on Fatigue Life of Thermal Turbine Generators in the Grid: A Frequency-Domain Approach

The School of Electrical Engineering and Computer Science, Penn State University(宾夕法尼亚州立大学电气与计算机工程学院);Department of Mechanical Engineering, Penn State University(宾夕法尼亚州立大学机械工程系);Tesla Inc.(特斯拉公司)

Fiaz Hossain, Nilanjan Ray Chaudhuri, Alok Sinha, Sai Gopal Vennelaganti, Mohammed E. Nassar

AI总结:

本文提出一种频域方法,通过分析人工智能数据中心负载变化对同步发电机涡轮机疲劳损伤的影响,建立评估框架并提出三步流程量化负载波动限制。

摘要:

本文建立了一个框架,用于评估人工智能(AI)数据中心(DC)负载变化对同步发电机(SG)蒸汽/燃气涡轮机疲劳损伤的影响。接着,提出一个简单的三步流程,通过频域分析来量化AI数据中心负载波动的限制。第一步,从第一原理确定每个SG终端的最大允许电力输出变化,仅需一个集中多质量模型来表示SG的机械部分。第二步,提出一种新的方法,利用负载流确定所谓的代数'交互因子',将给定节点的AI数据中心负载变化映射到每个SG功率输出的变化。第三步,提出一种筛选方法,对候选节点进行排序以安装AI数据中心,并解决一个优化问题以确定AI数据中心允许的波动范围。通过修改后的IEEE 4机和IEEE-68节点系统进行频域和时域分析来验证所提方法的适用性。最后,在合成的2000节点德克萨斯系统上展示了所提方法的可扩展性。

英文摘要:

A framework is established that assesses the impact of variations in artificial intelligence (AI) data center (DC) loads on the fatigue damage of steam/gas turbines of the synchronous generators (SGs) from torsional oscillations. Next, a simple three-step process that is supported by frequency-domain analysis is laid out to quantify the limits on fluctuations in AI DC loads. In the first step, the maximum allowable variation in electrical power output at each SG terminal is independently determined from the first principles. This step needs only a lumped multi-mass model of the mechanical side of the SG. In the second step, we propose a new approach that relies on load flow to determine the so-called algebraic `interaction factor' that maps the change in AI DC load at a given bus to the corresponding change in each of the SG power outputs. In the third step, we propose a screening method to rank the candidate buses to site AI DCs and solve an optimization problem to determine the optimal allowable fluctuations in the AI DCs. We demonstrate the applicability of the proposed approach through frequency-domain and time-domain analyses in the modified IEEE 4-machine and IEEE-68 bus systems using a dynamic phasor framework. Finally, we demonstrate the scalability of the proposed approach on the synthetic 2000-bus Texas system.