基于数字孪生的数据中心冷却系统优化

Digital Twin-Based Cooling System Optimization for Data Center

University of Michigan-Dearborn(密歇根大学迪尔伯恩分校)

Shrenik Jadhav, Zheng Liu

AI总结:

本文提出基于数字孪生的数据中心冷却系统优化方法,通过分层优化框架实现20.4%-30.1%的能耗节约,显著提升冷却效率。

摘要:

数据中心冷却系统消耗大量辅助能源,但优化研究很少量化理论最优与可部署控制策略之间的差距。本文开发了前沿exascale超级计算机液冷基础设施的数字孪生,其中高温水系统由三个并行子回路组成,每个子回路通过板式换热器和变频泵为专用冷却剂分配单元集群服务。该替代模型基于Modelica构建,并通过一年10分钟的操作数据验证,遵循ASHRAE指南14。模型实现了子回路均方误差系数变异低于2.7%和归一化平均偏差误差在2.5%以内。使用此验证的替代模型,分层优化框架评估了三种逐步约束策略:分析流仅优化实现20.4%的总能耗节约,无约束的流量和供温联合优化显示30.1%的总能耗节约,以及具有流量和供温梯度约束的优化,强制执行执行器速率限制,可达到27.8%的总能耗节约。分析显示,基线系统运行在2.9倍的最低热安全流量率,与流量联合优化的供温几乎使仅通过流量减少实现的节约翻倍。

英文摘要:

Data center cooling systems consume significant auxiliary energy, yet optimization studies rarely quantify the gap between theoretically optimal and operationally deployable control strategies. This paper develops a digital twin of the liquid cooling infrastructure at the Frontier exascale supercomputer, in which a hot-temperature water system comprises three parallel subloops, each serving dedicated coolant distribution unit clusters through plate heat exchangers and variable-speed pumps. The surrogate model is built based on Modelica and validated through one full calendar year of 10-minute operational data following ASHRAE Guideline 14. The model achieves a subloop coefficient of variation of the root mean square error below 2.7% and a normalized mean bias error within 2.5%. Using this validated surrogate model, a layered optimization framework evaluates three progressively constrained strategies: an analytical flow-only optimization achieves 20.4% total energy saving, unconstrained joint optimization of flow rate and supply temperature demonstrates 30.1% total energy saving, and ramp-constrained optimization of flow rate and supply temperature, enforcing actuator rate limits, can reach total energy saving of 27.8%. The analysis reveals that the baseline system operates at 2.9 times the minimum thermally safe flow rate, and the co-optimizing supply temperature with flow rate nearly doubles the savings achievable by flow reduction alone.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑