楼宇电动机保护对电力系统暂态行为的影响
Impact of Building-Level Motor Protection on Power System Transient Behaviors
摘要:
输电和配电系统的保护策略已被广泛研究,以促进更好地协调物理保护设备。具有专用保护方案的各种功能电机越来越多地用于商业、住宅和工业建筑。本文着重于模拟几个最流行的保护方案,使用电磁暂态程序(EMTP)模型的三相和单相感应电动机在现有的商业建筑连接到典型的配电馈线。为了研究单相电动机失速的行为,电动机保护和重新连接的动作,以及设备级保护对系统级动态的影响,我们在满载功能感应电动机的馈线头部施加电压抑制。几个配电馈线代表在一个标准的IEEE 39总线传输系统,模拟故障引起的延迟电压恢复(FIDVR),并探讨缓解策略,通过优化配置建筑物级电机保护设置。
英文摘要:
Protection strategies for transmission and distribution systems have been extensively investigated to facilitate better coordination of physical protection devices. A diverse range of functional motors with dedicated protection schemes are being used more and more in commercial, residential, and industrial buildings. This paper focuses on simulating several of the most popular protection schemes using the ElectroMagnetic Transient Program (EMTP) model for three-phase and single-phase induction motors in existing commercial buildings connected to typical distribution feeders. To investigate the behaviors of single-phase motors stalling, the actions of motor protection and reconnections, and the impacts of device-level protection on system-level dynamics, we imposed voltage depressions at the head of a feeder fully loaded with functional induction motors. Several distribution feeders are represented in a standard IEEE 39-bus transmission system to simulate fault-induced delayed voltage recovery (FIDVR) and explore mitigation strategies by optimally configuring the building-level motor protection settings.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。