arXivDaily arXiv每日学术速递 周一至周五更新
arXiv 2511.02084eess.SP
收藏

基于递归图和变化分位数的深度监督与半监督光伏电站连接输电线路保护方法

Recurrence Plot and Change Quantile-based Deep Supervised and Semi-supervised Protection for Transmission Lines Connected to Photovoltaic Plants

Western Kentucky University(西肯塔基大学);KIIT University(KIIT大学)

Pallav Kumar Bera, Samita Rani Pani

AI总结:

本文提出一种基于递归图与InceptionTime的单端智能保护方法,利用三相电流分位数变化识别故障,并结合半监督学习解决标签稀缺问题,有效保障光伏电站连接输电线路的安全。

摘要:

传统继电保护装置因电力电子设备对故障特征的影响,难以有效保护连接基于变换器的能源源(CBESs)的输电线路(TLs)。本文提出一种针对电网与光伏(PV)电站间TL段的单端智能保护方法。该方法利用递归矩阵和基于InceptionTime的系统,通过三相电流分位数的平均变化来识别故障,确定故障位置并识别故障相。采用ReliefF特征选择提取最优分位特征。该方案在WSCC 9节点系统上通过PSCAD/EMTDC仿真评估,涵盖故障、电容器及负荷投切等异常工况及多种参数。此外,方案还在New England IEEE 39节点系统及部分额定变换器场景下验证,并考虑双回线、噪声、串联补偿、高阻故障、CT饱和、发展性及跨线故障、远近端故障,以及PV容量、采样频率和数据窗尺寸变化等条件。为解决标签稀缺并提升泛化能力,将标签传播、标签扩散和自训练等半监督学习范式与InceptionTime框架集成,在有限标注故障数据下实现接近监督学习的性能。结果表明,该方法能有效应对不同系统配置与工况,确保大型PV电站连接TLs的保护。

英文摘要:

Conventional relays encounter difficulties in protecting transmission lines (TLs) connected to converter-based energy sources (CBESs) due to the influence of power electronics on fault characteristics. This article proposes a single-ended intelligent protection method for the TL segment between the grid and a Photovoltaic (PV) plant. The approach utilizes a Recurrence Matrix and an InceptionTime-based system to identify faults by using the mean change in quantiles of 3-phase currents. It determines the fault position and identifies the faulty phase. ReliefF feature selection is applied to extract the optimal quantile features. The scheme's performance is assessed under abnormal conditions, including faults and capacitor and load-switching events, simulated in Power Systems Computer Aided Design / Electromagnetic Transients Program (PSCAD/EMTDC) on the Western System Coordinating Council (WSCC) 9-bus system, with various fault and switching parameters. The scheme is also validated on the New England IEEE 39-bus system and in presence of partially rated converters. Additionally, the validation of the proposed strategy takes into account various conditions, including double-circuit line configuration, noise, series compensation, high-impedance faults, current transformer (CT) saturation, evolving and cross-country faults, remote and local faults, as well as variations in PV capacity, sampling frequency, and data window size. To address label scarcity and improve generalization, semi-supervised learning paradigms including label spreading, label propagation, and self-training are integrated with the InceptionTime framework, enabling near-supervised performance with limited annotated fault data. The results demonstrate that the approach is effective in handling different system configurations and conditions, ensuring the protection of TLs connected to large PV plants.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑