基于结构和物理的电力网络模型降阶方法

Structure- & Physics- Preserving Reductions of Power Grid Models

Nansen Environmental and Remote Sensing Center(纳森斯环境遥感中心);Los Alamos National Laboratory(洛斯阿拉莫斯国家实验室)

Colin Grudzien, Deepjyoti Deka, Michael Chertkov, Scott N Backhaus

AI总结:

本文研究了多尺度、配电网和输电网的降阶方法,通过图拓扑选择参考节点并聚合相干子网络,以保持电流并构建等效潮流网络,实现快速仿真和后续应用。

摘要:

多尺度、配电网和输电网的庞大尺寸阻碍了系统级估计和实时控制及优化。本文研究了适用于快速仿真的电网降阶方法。尽管经典的克罗内克降阶在传统分层设计中取得了成功,但在多尺度网络中选择参考节点变得模糊。在本文中,我们扩展了迭代克罗内克降阶的应用,利用电网的图拓扑来选择参考节点,与多尺度网络的设计特征一致。此外,我们通过聚合三角网格中的相干子网络进一步降阶,基于图拓扑和网络特性,以保持电流并构建另一个潮流等效网络。我们的降阶是通过使用包含一般树结构、线路和三角形的子图的迭代聚合来实现的。我们的降阶算法的重要特征包括:(i) 降阶要么等同于克罗内克降阶,要么产生潮流等效网络;(ii) 由于上述潮流等效性,降阶网络可以建模无损耗、感应、稳态网络的动态;(iii) 算法高效利用哈希表存储顺序降阶步骤。

英文摘要:

The large size of multiscale, distribution and transmission, power grids hinder fast system-wide estimation and real-time control and optimization of operations. This paper studies graph reduction methods of power grids that are favorable for fast simulations and follow-up applications. While the classical Kron reduction has been successful in reduced order modeling of power grids with traditional, hierarchical design, the selection of reference nodes for the reduced model in a multiscale, distribution and transmission, network becomes ambiguous. In this work we extend the use of the iterative Kron reduction by utilizing the electric grid's graph topology for the selection of reference nodes, consistent with the design features of multiscale networks. Additionally, we propose further reductions by aggregation of coherent subnetworks of triangular meshes, based on the graph topology and network characteristics, in order to preserve currents and build another power-flow equivalent network. Our reductions are achieved through the use of iterative aggregation of sub-graphs that include general tree structures, lines, and triangles. Important features of our reduction algorithms include that: (i) the reductions are, either, equivalent to the Kron reduction, or otherwise produce a power-flow equivalent network; (ii) due to the former mentioned power-flow equivalence, the reduced network can model the dynamic of the swing equations for a lossless, inductive, steady state network; (iii) the algorithms efficiently utilize hash-tables to store the sequential reduction steps.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑