The impacts of high PV penetration on distribution feeders have been well documented within the last decade. To mitigate these impacts, interconnection standards have been amended to allow PV inverters to regulate voltage locally. However, there is a deficiency of literature discussing how these inverters will behave on real feeders under increasing PV penetration. In this paper, we simulate several deployment scenarios of these inverters on a real California distribution feeder. We show that minimum and maximum voltage, tap operations, and voltage variability are improved due to the inverters. Line losses were shown to increase at high PV penetrations as a side effect. Furthermore, we find inverter sizing was shown to be important as PV penetration increased. Finally we show that increasing the number of inverters and removing the deadband from the Volt/VAr control curve improves the effectiveness.
The increase in grid-connected photovoltaic (PV) systems has been consistent over the years. Several studies have reported the impacts of this increase on the distribution networks such as reverse power flow, voltage fluctuations, possible increase in system losses amongst others. With this rise in PV penetration level, it becomes necessary for grid tied smart inverters (SI) to be allowed to participate in feeder voltage regulation. Till date, no comprehensive technical review and analysis has been done on the impact and interaction of existing and proposed SI settings on the existing legacy v…
Photovoltaic (PV) smart inverters can improve the voltage profile of distribution networks. A multi-objective optimization framework for coordination of reactive power injection of smart inverters and tap operations of on-load tap changers (OLTCs) for multi-phase unbalanced distribution systems is proposed. The optimization objective is to minimize voltage deviations and the number of tap operations simultaneously. A novel linearization method is proposed to linearize power flow equations and to convexify the problem, which guarantees convergence of the optimization and less computation costs.…
This paper presents a zonal Volt/VAR control scheme that coordinates Photovoltaic (PV) inverters for providing voltage regulation on 3-phase unbalanced distribution feeders. Voltage sensitivity studies are conducted to uncover the dependency between nodal voltage changes and the reactive power injections at nodes with smart PV inverters. A fast incremental clustering method is developed to divide the distribution feeder into weakly coupled zones based on correlations of nodal voltage sensitivities. Because each zone is weakly coupled, voltage of each zone can be controlled independently. Thus,…
To mitigate issues related to the growth of variable smart loads and distributed generation, distribution system operators (DSO) now make it binding for prosumers with inverters to operate under pre-set rules. In particular, the maximum active and reactive power set points for prosumers are based on local voltage measurements to ensure that inverter output does not cause voltage violations. However, such actions, as observed in this work, restrict the range available for local energy management, with more adverse losses on arbitrage profits for prosumers located farther away from the substatio…
This paper presents a two-stage zonal Volt/VAR control scheme for coordinating inverter-based resources (IBR) with utility-owned voltage regulators (VR) to regulate voltage in unbalanced 3-phase distribution systems. First, correlations between nodal voltages are derived from nodal voltage sensitivity studies. Then, the feeder is partitioned into non-overlapping, weakly-coupled voltage control zones based on nodal voltage correlations. IBR are used in the first stage to regulate voltage changes continuously and VR are used in the second stage to regulate large voltage deviations. An online VR …
This paper presents a novel hierarchical framework for real-time, network-admissible coordination of responsive grid resources aggregated into virtual batteries (VBs). In this context, a VB represents a local aggregation of directly controlled loads, such as smart inverters, electric water heaters, and air-conditioners. The coordination is achieved by solving an optimization problem to disaggregate a feeder's desired reference trajectory into constraint-aware set-points for the VBs. Specifically, a novel, provably-tight, convex relaxation of the AC optimal power flow (OPF) problem is presented…
In this work we explore impedance-based interactions that arise when inverter-connected distributed energy resources (DERs) inject real and reactive power to regulate voltage and power flows on three-phase unbalanced distribution grids. We consider two inverter control frameworks that compute power setpoints: a mix of volt/var and volt/watt control, and phasor-based control. On a two-bus network we isolate how line length, R/X ratio, and mutual impedances each affects the stability of the DER system. We validate our analysis through simulation of the two-bus network, and validate that the effe…
The renewable energy proliferation calls upon the grid operators and planners to systematically evaluate the potential impacts of distributed energy resources (DERs). Considering the significant differences between various inverter-based resources (IBRs), especially the different capabilities between grid-forming inverters and grid-following inverters, it is crucial to develop an efficient and effective assessment procedure besides available co-simulation framework with high computation burdens. This paper presents a streamlined graph-based topology assessment for the integrated power system t…
Voltage control devices are employed in power distribution systems to reduce the power consumption by operating the system closer to the lower acceptable voltage limits; this technique is called conservation voltage reduction (CVR). The different modes of operation for system's legacy devices (with binary control) and new devices (e.g. smart inverters with continuous control) coupled with variable photovoltaic (PV) generation results in voltage fluctuations which makes it challenging to achieve CVR objective. This paper presents a two-timescale control of feeder's voltage control devices to ac…
Quantifying the impact of inverter-based distributed generation (DG) sources on power-flow distribution system cases is arduous. Existing distribution system tools predominately model distributed generation sources as either negative PQ loads or as a PV generator and then employed a PV-PQ switching algorithm to mimic Volt/VAR support. These models neglect the unique characteristics of inverter-based distributed generation sources, have scalability and convergence issues, and are ill-suited for increasing solar penetration scenarios. This work proposes an inverter-based DG model accounting for …
Solar distribution feeders are commonly used in solar farms that are integrated into distribution substations. In this paper, we focus on a real-world solar distribution feeder and conduct an event-based analysis by using micro-PMU measurements. The solar distribution feeder of interest is a behind-the-meter solar farm with a generation capacity of over 4 MW that has about 200 low-voltage distributed photovoltaic (PV) inverters. The event-based analysis in this study seeks to address the following practical matters. First, we conduct event detection by using an unsupervised machine learning ap…
The high R/X ratio of typical distribution systems makes the system voltage vulnerable to the active power injection from distributed energy resources (DERs). Moreover, the intermittent and uncertain nature of the DER generation brings new challenges to the voltage control. This paper proposes a two-stage stochastic optimization strategy to optimally place the PV smart inverters with Volt-VAr capability for distribution systems with high photovoltaic (PV) penetration to mitigate voltage violation issues. The proposed optimization strategy enables a planningstage guide for upgrading the existin…
Power distribution grids with high PV generation are exposed to voltage disturbances due to the unpredictable nature of renewable resources. Smart PV inverters, if controlled in coordination with each other and continuously adapted to the real-time conditions of the generation and load, can effectively regulate nodal voltages across the feeder. This is a fairly new concept and requires communication and a distributed control logic to realize a fair utilization of reactive power across all PV systems. In this paper, a collaborative reactive power optimization is proposed to minimize voltage dev…
Volt-VAR and Volt-Watt functionality in photovoltaic (PV) smart inverters provide mechanisms to ensure system voltage magnitudes and power factors remain within acceptable limits. However, these control functions can become unstable, introducing oscillations in system voltages when not appropriately configured or maliciously altered during a cyberattack. In the event that Volt-VAR and Volt-Watt control functions in a portion of PV smart inverters in a distribution grid are unstable, the proposed adaptation scheme utilizes the remaining and stably-behaving PV smart inverters and other Distribut…
It is speculated that higher penetration of inverter-based distributed photo-voltaic (PV) power generators can increase the risk of tripping events due to voltage fluctuations. To quantify this risk utilities need to solve the interactive equations of tripping events for networked PVs in real-time. However, these equations are non-differentiable, nonlinear, and exponentially complex, and thus, cannot be used as a tractable basis for solar curtailment prediction and mitigation. Furthermore, load/PV power values might not be available in real-time due to limited grid observability, which further…
Autonomous droop control PV inverters have improved voltage regulation compared to the inverters without grid support functions, but more flexible control techniques will be required as the number of solar photovoltaic (PV) installations increases. This paper studies three inverter future deployment scenarios with droop control inverters, non-exporting inverters, and coordinated inverter control (CIC). The network operation and the interaction between various inverter control methods are studied by simulating inverter operation on two low-voltage networks. Considering 30% PV penetration as the…
Due to market, there is flexibility in the price for power purchase by the utility. At the maximum loading condition the cost of power is high, hence conservation voltage reduction (CVR) is a useful technique in reducing power demand of the distribution system. Further, by installing battery energy storage system (BESS) in the distribution system, power can be stored in the BESS when the price is low and can be utilize to supply the demand when the price is high. In this paper, power conserving and cost saving problems are investigated. As we consider loads in distribution system as voltage de…
The proliferation of distributed energy resources (DERs) im-poses new challenges to distribution system operation, e.g., power quality issues. To overcome these challenges and enhance system operation, it is critical to effectively utilize all available resources and accurately characterize unbalanced distribution networks in operational tools. This paper proposes a convex second-order-cone programming (SOCP)-based AC optimal power flow (ACOPF) model for three-phase unbalanced distribution net-works, including smart inverters and Volt-VAr controller (VVC) devices. Reactive power-voltage (Q-V) …
This paper addresses the problem of voltage regulation in a power distribution grid using the reactive power injections of grid-connected power inverters. We first discuss how purely local voltage control schemes cannot regulate the voltages within a desired range under all circumstances and may even yield detrimental control decisions. Communication and, through that, coordination are therefore needed. On the other hand, short-range peer-to-peer communication and knowledge of electric distances between neighbouring controllers are sufficient for this task. We implement such a peer-to-peer con…
We consider the problem of controlling the voltage of a distribution feeder using the reactive power capabilities of inverters. On a real distribution grid, we compare the local Volt/VAr droop control recommended in recent grid codes, a centralized dispatch based on optimal power flow (OPF) programming, and a feedback optimization (FO) controller that we propose. The local droop control yields suboptimal regulation, as predicted analytically. The OPF-based dispatch strategy requires an accurate grid model and measurement of all loads on the feeder in order to achieve proper voltage regulation.…
This paper proposes an asychronous distributed leader-follower control method to achieve conservation voltage reduction (CVR) in three-phase unbalanced distribution systems by optimally scheduling smart inverters of distributed energy resources (DERs). One feature of the proposed method is to consider integrated primary-secondary distribution networks and voltage dependent loads. To ease the computational complexity introduced by the large number of secondary networks, we partition a system into distributed leader-follower control zones based on the network connectivity. To address the non-con…
Network reconfiguration (NR) has attracted much attention due to its ability to convert conventional distribution networks (DNs) into self-healing grids. This paper proposes a new strategy for real-time voltage regulation (VR) in a reconfigurable DN, whereby optimal feedforward control of synchronous and inverter-based distributed generators (DGs) is achieved in coordination with the operation of feeder line switches (SWs). This enables preemptive compensation of upcoming deviations in DN voltages caused by NR-aided load restoration. A robust optimization problem is formulated using a dynamic …
Voltage unbalance in distribution networks (DN) is expected to grow with increasing penetration of single-phase distributed generation and single-phase loads such as electric vehicle chargers. Unbalance mitigation will be a significant concern as voltage unbalance leads to increased losses, reduced motor and inverter efficiency, and becomes a limiting factor for DN operation. The true definition of the unbalance metric needs phasor measurements of network voltage and current. However, such phasor measurements are generally not available in real life and as such approximate definitions are wide…