基于图神经网络的电流互感器物理信息动态状态估计

Physics-Informed Dynamic State Estimation for Current Transformers Using Graph Neural Networks

Georgia Institute of Technology(佐治亚理工学院);Syracuse University(雪城大学)

Michael A. Boateng, Gabriel Gauderman, Nathalie Uwamahoro

AI总结:

研究电流互感器动态状态估计问题,用COMTRADE测量值,通过构建结构化基准对比不同方案,用图神经网络改进初始化,提升估计器性能,增强CT饱和校正鲁棒性。

摘要:

电流互感器对电力系统保护和测量至关重要,暂态铁心饱和会扭曲二次电流并降低测量精度。现有方法初始化未考虑物理依赖结构。本文利用WinIGS-T生成的COMTRADE测量值对电流互感器动态状态估计进行物理信息增强,提出的热启动策略提升了估计器性能。

英文摘要:

Current transformers are fundamental to power system protection and measurement, yet transient core saturation can severely distort the secondary current and degrade measurement accuracy. Existing dynamic state estimation methods rely mainly on numerical discretisation and iterative solvers, but their initialisation is not informed by the physical dependency structure of the estimation problem, which limits robustness under noisy conditions. This paper presents a physics-informed enhancement for current transformer dynamic state estimation using COMTRADE measurements generated in WinIGS-T. A structured benchmark of four discretisation schemes and three iterative solvers identifies Gauss-Newton with Quadratic discretisation as the strongest baseline. To address the limitation of conventional cold-start initialisation, a graph neural network is constructed from the Jacobian sparsity pattern to generate physics-informed initial state estimates. The proposed warm-start strategy improves estimator conditioning and achieves average gains of 25% in initialisation distance and 38% in initial weighted objective value across all tested SNR levels. The results demonstrate that embedding physical structure into the initialisation stage improves the robustness of CT saturation correction and supports more reliable measurement and protection performance in modern power grids.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑