生成式自主电网控制:决策变压器与两阶段安全堆栈的集成

Generative Autonomous Grid Control: Integrating Decision Transformers with a Two-Stage Safety Stack

Ain Shams University(艾因夏姆斯大学)

Mohamed Shamseldein

AI总结:

提出一种结合离线训练决策变压器与两阶段符号安全堆栈的自主电网频率控制框架,在低惯性条件下将区域控制误差积分降低99%以上,并维持59.4 Hz频率最低点。

摘要:

基于逆变器的资源对同步发电的替代正在加速电力系统频率动态,使其超出传统自动发电控制的响应能力。本文提出了自主电网发电控制与决策变压器框架,该框架将离线训练的决策变压器与用于二次频率控制的两阶段符号安全堆栈相结合。决策变压器通过序列建模从离线监控和数据采集记录中学习条件调度策略,消除了在线探索风险。约束验证单元利用实时功率传输分布因子提供亚十毫秒代数筛选,而聚合数字孪生执行基于摆动方程的动态稳定性认证。在东北电力协调委员会140节点系统低惯性条件下验证,所提出的控制器相对于调谐的自动发电控制将区域控制误差积分降低了99%以上,维持59.4 Hz频率最低点,推理延迟约10毫秒,完全满足实时约束。与线性二次调节器基线的比较评估以及针对保守Q学习的结构分析证明了序列建模公式的优势。小信号特征值分析表征了主导的1.87 Hz机电模式,并确认安全堆栈在运行点之间保持稳定运行。每当提案被拒绝时,安全堆栈回退到调谐的自动发电控制,从而在仿真中将最坏情况性能限制在行业标准水平。

英文摘要:

The displacement of synchronous generation by inverter-based resources is accelerating power system frequency dynamics beyond the response capability of conventional automatic generation control. This paper presents Autonomous Grid Generation Control with Decision Transformers, a framework coupling an offline-trained Decision Transformer with a twostage symbolic safety stack for secondary frequency control. The Decision Transformer learns a conditional dispatch policy from offline supervisory control and data acquisition records via sequence modeling, eliminating online exploration risks. A Constraint Verification Unit provides sub-ten-millisecond algebraic screening using real-time power transfer distribution factors, while an aggregate digital twin performs swing-equation-based dynamic stability certification. Validated on the Northeast Power Coordinating Council 140-bus system under low-inertia conditions, the proposed controller reduces the area control error integral by over 99% relative to tuned automatic generation control, maintains a 59.4 Hz frequency nadir, and achieves inference latency of approximately 10 ms, well within real-time constraints. Comparative evaluation against a linear quadratic regulator baseline and structural analysis against conservative Q-learning demonstrate the advantages of the sequence-modeling formulation. Small-signal eigenvalue analysis characterizes the dominant 1.87 Hz electromechanical mode and confirms that the safety stack maintains stable operation across operating points. By falling back to tuned automatic generation control whenever proposals are rejected, the safety stack bounds worst-case performance to industry-standard levels in simulation.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑