基于终端测量的三相负载等效的几何时域辨识

Geometric Time-Domain Identification of Three-Phase Load Equivalents from Terminal Measurements

University of Almeria(阿尔梅里亚大学);New York University(纽约大学)

Francisco G. Montoya, Francisco de Leon, Francisco M. Arrabal-Campos, Alfredo Alcayde

AI总结:

提出一种几何时域方法,利用瞬时电压电流测量轨迹在欧几里得信号空间中的几何特性辨识三相负载等效参数,适用于三线和四线系统,通过采样数据实现并包含可辨识性测试与无源性约束。

摘要:

本文提出了一种几何时域方法,用于从公共耦合点的瞬时电压和电流测量中辨识三相负载等效。测量波形被解释为欧几里得信号空间中的轨迹,负载等效参数从这些轨迹的几何中恢复。该方法将先前发表的单相几何辨识公式扩展到三线和四线系统,并特别强调三线情况,其中没有中性点电压测量,终端数据必须满足耦合的基尔霍夫约束。与早期解析公式相比,主要进步在于基于局部时间窗口、归一化矩阵方程、谐波投影导数和原始坐标、显式几何可辨识性测试、无源性约束以及能量/基尔霍夫残差的采样数据实现。当测量轨迹缺乏足够信息时,该方法不强制拟合模型,而是将低秩或病态窗口报告为低置信度证据。使用干净数据、测量噪声、窗口长度扫描和传感器延迟的数值模拟表明,该方法能准确辨识信息丰富的三相轨迹,并揭示结构退化情况,例如高阶三线模型的纯单频激励。对于给定的可接受拓扑,辨识出的电路在分析窗口内闭合了测量负载的瞬时终端能量平衡。

英文摘要:

This paper presents a geometric time-domain method for identifying three-phase load equivalents from instantaneous voltage and current measurements at the point of common coupling. Measured waveforms are interpreted as trajectories in Euclidean signal spaces, and load-equivalent parameters are recovered from the geometry of those trajectories. The method extends a previously published single-phase geometric identification formulation to three- and four-wire systems and places special emphasis on the three-wire case, where no neutral voltage is measured and the terminal data must satisfy coupled Kirchhoff constraints. The main advance over the earlier analytical formulation is a sampled-data implementation based on local time windows, normalized matrix equations, harmonic-projection derivative and primitive coordinates, explicit geometric identifiability tests, passivity constraints, and energy/Kirchhoff residuals. The method does not force a model when the measured trajectory lacks enough information; instead, it reports low-rank or ill-conditioned windows as low-confidence evidence. Numerical simulations with clean data, measurement noise, window-length sweeps, and sensor delay show that the method accurately identifies informative three-phase trajectories and exposes structurally degenerate cases such as pure single-frequency excitation for higher-order three-wire models. For a given admissible topology the identified circuit closes the instantaneous terminal energy balance of the measured load over the analysis window.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑