确定用于冷却的最优热能存储充电温度:结合建筑和铜管建模
Determining optimal thermal energy storage charging temperature for cooling using integrated building and coil modeling
AI总结:
本研究提出基于物理的集成模拟框架,通过优化 TES 充电温度提升热泵能效比,同时保持室内温度稳定。
摘要:
热能存储(TES)系统与热泵结合,通过将电力需求转移至非高峰时段,具有显著提高建筑能源效率的潜力。然而,传统操作策略在整个冷却季节内维持保守的低温冷水温度,这种做法导致热泵性能不 optimal。本研究提出了一种基于物理的集成模拟框架,以确定在确保冷却稳定性的前提下,可行的最高冷水供应温度。该框架整合了四个子模型:相对湿度预测、动态冷却负荷估计、冷却铜管性能预测以及 TES 放电温度预测。通过验证办公室建筑的测量数据,证明了所有子模型的可靠性(例如,冷却负荷的 CVRMSE 为 9.3%,峰值时间放电温度的 R2 为 0.91)。集成模拟表明,所提出的框架可将每日初始 TES 充电温度平均提高 2.55°C,相比传统固定温度操作,使热泵在更高的能效比下运行。本研究贡献了一种在保持室内设定温度的同时优化 TES 充电温度的实用方法,用于建筑供暖、通风和空气调节(HVAC)系统。
英文摘要:
Thermal energy storage (TES) systems coupled with heat pumps offer significant potential for improving building energy efficiency by shifting electricity demand to off-peak hours. However, conventional operating strategies maintain conservatively low chilled water temperatures throughout the cooling season, a practice that results in suboptimal heat pump performance. This study proposes a physics-based integrated simulation framework to determine the maximum feasible chilled water supply temperature while ensuring cooling stability. The framework integrates four submodels: relative humidity prediction, dynamic cooling load estimation, cooling coil performance prediction, and TES discharge temperature prediction. Validation against measured data from an office building demonstrates reliable accuracy across all sub-models (e.g., CVRMSE of 9.3% for cooling load and R2 of 0.91 for peak-time discharge temperature). The integrated simulation reveals that the proposed framework can increase the daily initial TES charging temperature by an average of 2.55 °C compared to conventional fixed-temperature operation, enabling the heat pump to operate at a higher coefficient of performance. This study contributes a practical methodology for optimizing TES charging temperatures in building heating, ventilation, and air conditioning (HVAC) systems while maintaining indoor setpoint temperatures.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。