大规模跨区域电力流下的输电网稳定性

Transmission grid stability with large interregional power flows

María Martínez-Barbeito, Damià Gomila, Julian Fritzsch, Philippe Jacquod, Pere Colet

AI总结:

提出识别大型电网长距离输电关键线路的通用方法,发现跨区域电力流超临界值时因拓扑约束引发失稳,并揭示两种失稳场景,识别出的关键线路与2021年欧洲电网实际分离事件吻合。

摘要:

我们提出了一种通用方法,用于识别大型电网长距离输电中的关键线路。当系统被推向运行极限时(例如由高比例可变可再生能源接入产生的大规模功率不平衡),网络会失去稳定性和同步性。我们研究了欧洲大陆同步交流电网在可调大规模跨区域电力流下的模型。当这些电力流超过某个临界值时,我们发现由于拓扑约束会出现不稳定现象。我们识别出触发这些不稳定性的两种不同场景。在第一种场景中,特定的线路组同时达到其最大负载,导致电网分裂为两个失步区域。在第二种场景中,一条或少数几条线路过载,最终导致一个 Lyapunov 指数变为正值。第一种场景显然缺乏普适性,我们开发了一种数值方法来强制将交流电网分裂为断开的区域。值得注意的是,以这种方式识别出的关键线路,与 2021 年两次触发欧洲大陆同步电网分离事件的实际线路相吻合。我们进一步讨论了系统的模态如何提供信息,以说明哪些区域更容易相互失去同步性。

英文摘要:

We propose a general methodology for identifying critical lines in the long-distance transmission of power across large electric grids. When the system is pushed to its operational limit, for instance by large power imbalances such as those generated by high penetration of variable renewable energy sources, the network gets destabilized and loses synchrony. We investigate a model of the synchronous AC grid of continental Europe under tunable large interregional power flows. When those flows exceed some critical value, we find that instabilities emerge due to topological constraints. We identify two different scenarios triggering these instabilities. In the first one, specific sets of lines reach their maximal load simultaneously, causing the grid to split into two desynchronized zones. In the second one, one or few lines become overloaded, which eventually renders one Lyapunov exponent positive. The first scenario is obviously less generic and we develop a numerical approach to force the splitting of the AC grid into disconnected areas. Remarkably, the critical lines identified in this way match those that triggered the separation of the synchronous grid of continental Europe in two instances in 2021. We further discuss how the modes of the system provide information on which areas are more susceptible to lose synchrony with each other.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑