提出了一种基于参数误差模型和两步逐相加权最小二乘状态估计(SE)的故障诊断模型。该方案利用相量测量单元和合成测量来识别每相潮流和注入测量,通过应用于合成测量误差(CME)的$χ^2$假设检验来指示参数误差。虽然电流和电压波形通常分析高阻抗故障检测,广域功率流和注入测量,这已经是固有的SE过程,也显示了现实世界的高阻抗故障检测应用的前景。检测后的误差分布共享在已证明的参数误差诊断中观察到的测量函数误差扩展,并且可以应用于HIF识别。此外,将从测量误差中清楚地辨别与HIF相关的该误差扩散。在Simulink中对33节点配电系统进行了案例研究。

英文摘要:

This paper presents a model for detecting high-impedance faults (HIFs) using parameter error modeling and a two-step per-phase weighted least squares state estimation (SE) process. The proposed scheme leverages the use of phasor measurement units and synthetic measurements to identify per-phase power flow and injection measurements which indicate a parameter error through $χ^2$ Hypothesis Testing applied to the composed measurement error (CME). Although current and voltage waveforms are commonly analyzed for high-impedance fault detection, wide-area power flow and injection measurements, which are already inherent to the SE process, also show promise for real-world high-impedance fault detection applications. The error distributions after detection share the measurement function error spread observed in proven parameter error diagnostics and can be applied to HIF identification. Further, this error spread related to the HIF will be clearly discerned from measurement error. Case studies are performed on the 33-Bus Distribution System in Simulink.