考虑能量存储、电动汽车和能量共享的建筑群的协调控制以提高性能

A coordinated control to improve performance for a building cluster with energy storage, electric vehicles, and energy sharing considered

Pei Huang, Marco Lovati, Xingxing Zhang, Chris Bales

摘要:

分布式可再生能源系统现在广泛安装在许多建筑物中,将建筑物转变为电力生产者。现有的研究已经开发了一些先进的建筑侧控制,这些控制可以实现可再生能源共享,并旨在通过调节储能充电/放电来优化建筑群级性能。然而,在这些建筑物侧控制中没有考虑电动汽车的灵活需求转移能力。例如,电动汽车充电通常会在插入充电站后开始。但是,在这样的充电期间,可再生能源发电可能不足以覆盖EV充电负载,导致电网电力输入。因此,建筑集群级别的性能没有得到优化。因此,本研究提出了一种协调控制的建筑prosumers提高集群级性能,利用能源共享和存储能力的电池在建筑物和电动汽车。首先建立了电动汽车充放电模型。然后,基于预测的未来24小时电力需求和可再生能源发电数据,协调控制首先将整个建筑群视为一个集成建筑,并使用遗传算法优化其操作以及EV充电/放电。接下来,使用非线性规划来协调各个建筑物在未来24小时内的运行。为了验证,开发的控制已在瑞典卢德维卡的一个真正的建筑群进行了测试。研究结果表明,与传统控制方法相比,该控制方法可使集群级日可再生能源自耗率提高19%,同时降低日电费36%。

英文摘要:

Distributed renewable energy systems are now widely installed in many buildings, transforming the buildings into electricity prosumers. Existing studies have developed some advanced building side controls that enable renewable energy sharing and that aim to optimise building-cluster-level performance via regulating the energy storage charging/ discharging. However, the flexible demand shifting ability of electric vehicles is not considered in these building side controls. For instance, the electric vehicle charging will usually start once they are plugged into charging stations. But, in such charging period the renewable generation may be insufficient to cover the EV charging load, leading to grid electricity imports. Consequently, the building-cluster-level performance is not optimised. Therefore, this study proposes a coordinated control of building prosumers for improving the cluster-level performance, by making use of energy sharing and storage capability of electricity batteries in both buildings and EVs. An EV charging/discharging model is first developed. Then, based on the predicted future 24h electricity demand and renewable generation data, the coordinated control first considers the whole building cluster as one integrated building and optimises its operation as well as the EV charging/discharging using genetic algorithm. Next, the operation of individual buildings in the future 24h is coordinated using nonlinear programming. For validation, the developed control has been tested on a real building cluster in Ludvika, Sweden. The study results show that the developed control can increase the cluster-level daily renewable self-consumption rate by 19% and meanwhile reduce the daily electricity bills by 36% compared with the conventional controls.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑