The present distribution grids generally have limited sensing capabilities and are therefore characterized by low observability. Improved observability is a prerequisite for increasing the hosting capacity of distributed energy resources such as solar photovoltaics (PV) in distribution grids. In this context, this paper presents learning-aided low-voltage estimation using untapped but readily available and widely distributed sensors from cable television (CATV) networks. The CATV sensors offer timely local voltage magnitude sensing with 5-minute resolution and can provide an order of magnitude more data on the state of a distribution system than currently deployed utility sensors. The proposed solution incorporates voltage readings from neighboring CATV sensors, taking into account spatio-temporal aspects of the observations, and estimates single-phase voltage magnitudes at all non-monitored buses using random forest. The effectiveness of the proposed approach was demonstrated using a 1572-bus feeder from the SMART-DS data set for two case studies - passive distribution feeder (without PV) and active distribution feeder (with PV). The analysis was conducted on simulated data, and the results show voltage estimates with a high degree of accuracy, even at extremely low percentages of observable nodes.
There is a trade-off between transient performance and line current distortion of the DC bus voltage control of single-phase grid-connected voltage source converters. This paper presents an improved DC bus voltage control scheme of such converters using a proportional-integral controller in series with a first-order low pass filter. The extended symmetrical tuning method was adopted in the design of a regulator parameter, which greatly reduced the oscillating component at the double line frequency. The proposed control methodology allowed the loop bandwidth to increase without distorting the l…
The decarbonization of for example the energy or heat sector leads to the transformation of distribution grids. The expansion of decentralized energy resources and the integration of new consumers due to sector coupling (e.g. heat pumps or electric vehicles) into low voltage grids increases the need for grid expansion and usage of flexibilities in the grid. A high observability of the current grid status is needed to perform these tasks efficiently and effectively. Therefore, there is a need to increase the observability of low voltage grids by installing measurement technologies (e.g. smart m…
A high share of distributed photovoltaic (PV) generation in low-voltage networks may lead to over-voltage, and line/transformer overloading. To mitigate these issues, we investigate how advanced electricity tariffs could ensure safe grid operation hile enabling building owners to recover their investment in a PV and storage system. We show that dynamic volumetric electricity prices trigger economic opportunities for large investments in PV and battery capacity but lead to more pressure on the grid while capacity and block rate tariffs mitigate over-voltage and decrease line loading issues. How…
Virtual oscillator control is the latest control technique for grid-forming inverters. Virtual Oscillator based Controllers (VOCs) provide all the steady-state droop functionalities of conventional droop controllers and, in addition, the time-domain synchronization with a connected electrical network. However, existing literature does not consider the aspect of dynamic control over the voltage stiffness of a VOC. Voltage stiffness is a vital parameter for a grid-forming inverter. If the voltage stiffness is too high, the inverter picks up all the reactive power demand of the PCC. In contrast, …
The effective way of energy transmission plays a key factor in improving the overall transmission systems efficiency. Many methods are proposed to control the reactive power flow, voltage fluctuations and power factor improvement, The proposed converter topology gives a much significant improvement in transmission systems performance which includes multistage transformers control with the controlled converters along with the series active filters. The overall control strategy which involves the Multistage Voltage Re-Injection Transformer Controlled Converters (MSVRITCC) to reinject the voltage…
The renewable energy is connected to the power grid through power electronic converters, which are lack of make the inertia of synchronous generator/machine (SM) be lost. The increasing penetration of renewable energy in power system weakens the frequency and voltage stability. The Grid-Forming Converters (GFCs) simulate the function of synchronous motor through control method in order to improve the stability of power grid by providing inertia and stability regulation mechanism. This kind of converter control methods include virtual synchronous machine, schedulable virtual oscillator control …
Design and implementation of an optimal and robust single-loop voltage controller is proposed for single-phase grid forming voltage source inverter (VSI). The objective of the proposed controller is to have good reference tracking and disturbance rejection. Uncertain nature of loads can significantly alter system's behavior, especially during heavily loaded conditions, and impose an uncertainty in the dynamic model. This deteriorates the robustness of the controller severely. H-Infinity-based controller design is proposed in this article to address this issue. The required objectives of the op…
This paper proposes a novel strategy for the current injection based control for distributed energy resources connected to weak grids through a voltage source converter experiencing faults. The current injection controller is no longer synchronized with the point of common coupling at which the measured voltage signal can be severely affected by faults in the weak grid, but with the strong grid point at which the voltage is rigid. It is shown that the phase difference between the voltage source converter and the strong grid voltages caused by the long power lines does not affect the power cont…
In a purely inverter-based microgrid, both grid-forming (GFM) and grid-following (GFL) inverters will have a crucial role to play in frequency/voltage regulation and maintaining power sharing through their grid support capabilities. Consequently, the coordination between these two technologies becomes increasingly important for optimal system performance. However, the existing work does not consider GFL's potential to participate in a secondary control in coordination with GFM, thus not able to utilize the full capability of inverter resources. In this paper, we show that it is possible to ful…
This paper presents a novel grid-forming voltage control strategy for a battery energy storage system to maintain balanced three-phase output voltages when serving unbalanced loads. A stationary reference frame ($αβ$) based control scheme is proposed to regulate positive-sequence and negative-sequence voltages. Compared with the conventional rotating reference frame ($dq$) based control scheme, the proposed scheme shows better dynamic performance. Then, we analyze the system zero-sequence network and propose adding a grounding transformer to the Y/Yg connected output transformer to further red…
Dynamic Voltage Restorer (DVR), for some important reasons, is utilized in Power Distribution for protecting loads especially critical loads against some power quality issues like sag, swell, harmonics and faults. Fast transient response for compensating voltage quality is an unavoidable factor. Different control topologies have been applied to this device. In this project, a DVR is deployed to preserve a critical load that is connected in parallel with the grid and A wind turbine. Several situations of power quality issues have been considered. The simulation results of a proposed system that…
The converter control functions to provide the capabilities similar to synchronous generators are referred to as grid forming converters (GFC). Identical to a synchronous machine, a grid forming converter is expected to behave as a voltage source behind an impedance beyond the control bandwidth. However, GFC's realization has been different, with some utilizes inner current and voltage controllers while others do not. This paper studies the impact of the inner loop on the grid forming converter's ability to behave as a voltage source behind an impedance. Three of the most popular GFC structure…
In this paper we are interested in the problem of adaptive synchronization of a voltage source converter with a possibly weak grid with unknown angle and frequency, but knowledge of its parameters. To guarantee a suitable synchronization with the angle of the three-phase grid voltage we design an adaptive observer for such a signal requiring measurements only at the point of common coupling. Then we propose two alternative certainty-equivalent, adaptive phase-locked loops that ensure the angle estimation error goes to zero for almost all initial conditions. Although well-known, for the sake of…
As a consequence of the transition to distributed and renewable energy systems, some distribution system operators are increasingly concerned about power quality, including steady-state voltage volatility. In this paper, we study the control of real and reactive power injections by inverter-based distributed energy resources to regulate voltage magnitudes and phase angles measured by sensors positioned across 3-phase unbalanced distribution grids. Our proposed controllers are agnostic to the location and type of communications supporting energy resource operations. To design the controllers, w…
OptiQU: Coordinated Multi-Level Voltage and Reactive Power Control for Enhanced Voltage Quality and Secure Grid Operation
Fraunhofer Institute for Energy Economics and Energy System Technology IEE(弗劳恩霍夫能源经济学和能源系统技术研究所);University of Kassel(卡塞尔大学);Mitteldeutsche Netzgesellschaft Strom mbH(中德电网公司);Thüga AG(蒂古股份公司);Thüga Energienetze GmbH(蒂古能源网络有限公司);TU Dortmund University(多特蒙德工业大学);Maschinenfabrik Reinhausen GmbH(莱因豪森机械厂有限公司);EnSolVision GmbH(恩索尔视觉有限公司);Dipl.-Ing. H. Horstmann GmbH(H. 霍斯曼工程技术有限公司)
This work presents an optimization framework to aggregate the power and energy flexibilities in an interconnected power distribution systems. The aggregation framework is used to compute the day-ahead dispatch plans of multiple and interconnected distribution grids operating at different voltage levels. Specifically, the proposed framework optimizes the dispatch plan of an upstream medium voltage (MV) grid accounting for the flexibility offered by downstream low voltage (LV) grids and the knowledge of the uncertainties of the stochastic resources. The framework considers grid, i.e., operationa…
Voltage and Frequency Stability Analysis of Transmission Power Grids with EV Charging Stations
King Fahd University of Petroleum & Minerals (KFUPM)(国王法赫德石油与矿物大学);Interdisciplinary Research Center for Sustainable Energy Systems (IRC-SES), KFUPM(可持续能源系统交叉研究中心);SDAIA-KFUPM Joint Research Center for Artificial Intelligence, KFUPM(沙特数据与人工智能局-国王法赫德石油与矿物大学人工智能联合研究中心);Georgia Institute of Technology(佐治亚理工学院);RMIT University(皇家墨尔本理工大学)
As more distributed energy resources (DERs) are connected to the power grid, it becomes increasingly important to ensure safe and effective coordination between legacy voltage regulation devices and inverter-based DERs. In this work, we show how a distribution circuit model, composed of two LTCs and two inverter devices, can create voltage oscillations even with reasonable choices of control parameters. By modeling the four-device circuit as a switched affine hybrid system, we analyze the system's oscillatory behavior, both during normal operation and after a cyber-physical attack. Through the…
This study proposes a real-time distributed energy resource (DER) coordination model that can exploit flexibility from the DERs to solve voltage and overloading issues using both active and reactive power. The model considers time-coupling devices including electric vehicles and heat pumps by deviating as little as possible from their original schedules while prioritizing DERs with the most urgent demand using dynamic cost terms. The model does not require a multi-period setting or a multi-period-ahead forecast, which enables the model to alleviate the computational difficulty and enhance its …
The energy transition towards renewable based power provision requires improved monitoring and control of distributed energy resources (DERs), installed predominantly at the distribution grid level. Due to the gradual phase out of thermal generation, a shift of ancillary services provision like voltage control, congestion management and dynamic support from DERs is underway. Increased planning for procurement of ancillary services from underlying grid levels is required. Therefore, provision of flexible active and reactive power potentials from distribution system operators to transmission sys…
In recent times, non-intrusive load monitoring (NILM) has emerged as an important tool for distribution-level energy management systems owing to its potential for energy conservation and management. However, load monitoring in smart building environments is challenging due to high variability of real-time load and varied load composition. Furthermore, as the volume and dimensionality of smart meters data increases, accuracy and computational time are key concerning factors. In view of these challenges, this paper proposes an improved NILM technique using multi-head (Mh-Net) convolutional neura…
This paper presents the operation modes and control architecture of the grid-connected hydrogen electrolyzer systems for the provision of frequency and voltage supports. The analysis is focused on the primary and secondary loops in the hierarchical control scheme. At the power converter inner control loop, the voltage- and current-control modes are analyzed. At the primary level, the droop and opposite droop control strategies to provide voltage and frequency support are described. Coordination between primary control and secondary, tertiary reserves is discussed. The case studies and real-tim…
Volt-VAR and Volt-Watt functionality in photovoltaic (PV) smart inverters provide mechanisms to ensure system voltage magnitudes and power factors remain within acceptable limits. However, these control functions can become unstable, introducing oscillations in system voltages when not appropriately configured or maliciously altered during a cyberattack. In the event that Volt-VAR and Volt-Watt control functions in a portion of PV smart inverters in a distribution grid are unstable, the proposed adaptation scheme utilizes the remaining and stably-behaving PV smart inverters and other Distribut…
Power distribution grids with high PV generation are exposed to voltage disturbances due to the unpredictable nature of renewable resources. Smart PV inverters, if controlled in coordination with each other and continuously adapted to the real-time conditions of the generation and load, can effectively regulate nodal voltages across the feeder. This is a fairly new concept and requires communication and a distributed control logic to realize a fair utilization of reactive power across all PV systems. In this paper, a collaborative reactive power optimization is proposed to minimize voltage dev…
Disturbance-Observer-Based Grid-Forming Control for Unbalanced Grids
Aalto University School of Electrical Engineering(阿尔托大学电气工程学院);ABB Oy Drives(ABB驱动器公司);ABB Corporate Research(ABB企业研究院);Aix Marseille Univ, CNRS, LIS(艾克斯-马赛大学、法国国家科学研究中心、LIS实验室)
Having sufficient grid-forming sources is one of the necessary conditions to guarantee the stability in a power system hosting a very large share of inverter-based generation. The grid-forming function has been historically fulfilled by synchronous machines. However, with the appropriate control, it can also be provided by voltage source converters (VSC). This work presents a comparison between two technologies with grid-forming capability: the VSC with a grid-forming control coupled with an adequate energy storage system, and the synchronous condensers (SC). Both devices are compared regardin…
This paper reviews Voltage-Source Converters (VSCs) EMT and Phasor models currently used to simulate converter-interfaced generation (CIG) and renewable energy resources integration to power systems. Several modelling guidelines and suitability analyses were provided based on a comprehensive comparative study among the models. Various studies were performed in a small system and a large system, modelled in Simulink. We address a gap related to the suitability of CIGs phasor models in studies where the boundary between electromagnetic and electromechanical transients overlap. An insightful anal…
This article proposes the design of H-infinity-based robust current controller for single-phase grid-feeding voltage source inverter with an LCL filter. The main objective of the proposed controller is to have good reference tracking, disturbance rejection and sufficient LCL resonance damping under a large range of variations of grid impedance. Based on the aforementioned performance requirements, frequency dependent weighting functions are designed. Subsequently, the sub-optimal control problem is formulated and solved to determine the stabilizing controller. Computational footprint of the co…
With the increasing interest in converter-fed islanded microgrids, particularly for resilience, it is becoming more critical to understand the dynamical behavior of these systems. This paper takes a holistic view of grid-forming converters and considers control approaches for both modeling and regulating the DC-link voltage when the DC-source is a battery energy storage system. We are specifically interested in understanding the performance of these controllers, subject to large load changes, for decreasing values of the DC-side capacitance. We consider a fourth, second, and zero-order model o…
The deployment of distributed photovoltaics (PV) in low-voltage networks may cause technical issues such as voltage rises, line ampacity violations, and transformer overloading for distribution system operators (DSOs). These problems may induce high grid reinforcement costs. In this work, we assume the DSO can control each prosumer's battery and PV system. Under such assumptions, we evaluate the cost of providing flexibility and compare it with grid reinforcement costs. Our results highlight that using distributed flexibility is more profitable than reinforcing a low-voltage network until the …