arXivDaily arXiv每日学术速递 周一至周五更新
arXiv 2002.11209eess.SYcs.SY

Zero-inertia Systems: Sufficient Conditions for Phasor Modeling

Georgios Misyris, Spyros Chatzivasileiadis, Tilman Weckesser

英文摘要:

Time-domain simulations are a critical tool for power system operators. Depending on the instability mechanism under consideration and the system characteristics, such as the time constants of controllers, either phasor or Electro-Magnetic Transient (EMT) models should be employed. On the one hand, EMT models provide a detailed-modeling of the system dynamics, thus increase the reliability of stability analysis; on the other end, using these models increase the computational times of simulations, slowing down the security assessment process. To decrease computational time, system operators could resort to phasor-mode simulations for a (hopefully large) subset of disturbances. This paper investigates the appropriateness of phasor-approximation models on simulating events related to power supply and balance stability in zero-inertia systems. First, the stability boundaries, which each model is able to identify, are analyzed; then sufficient conditions for control parameters are derived, which allow using phasor-approximation models to monitor power sharing among grid-forming converter-based resources. Time-domain simulations are performed in PowerFactory DigSilent to verify the results.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑