不平衡多相配电网拓扑估计与节点相位识别

Unbalanced Multi-Phase Distribution Grid Topology Estimation and Bus Phase Identification

Stanford University(斯坦福大学);Arizona State University(亚利桑那州立大学)

Yizheng Liao, Yang Weng, Guangyi Liu, Zhongyang Zhao, Chin-woo Tan, Ram Rajagopal

AI总结:

本文提出了一种基于信息论的方法,利用智能电表数据估计配电网的多相拓扑并识别节点相位,通过将不平衡系统转换为对称分量并证明Chow-Liu算法在存在错误节点相位标签时能确定拓扑结构,最终通过Carson方程证明电压测量可正确识别节点相位连接,实验结果表明该方法在强负载不平衡和分布式能源接入条件下具有高准确性。

摘要:

随着分布式能源资源带来的不确定性在配电网中增加,准确的多相拓扑是相关不平衡配电网测量的基础。然而,由于投资有限,尤其是低压配电网,此类拓扑知识往往不可用。此外,由于人为错误或过时记录,节点相位标签信息不准确。为此,本文利用智能电表数据提出了一种信息论方法来学习配电网拓扑。具体而言,多相不平衡系统被转换为对称分量,即正序、负序和零序。然后,本文证明Chow-Liu算法通过利用功率流方程和由配电网径向多相结构隐含的条件独立关系来确定拓扑。最后,通过Carson方程证明可以使用电压测量正确识别节点相位连接。为验证,使用三个真实数据集模拟IEEE系统。仿真结果表明,该算法在强负载不平衡和DERs条件下仍能准确找到多相拓扑,确保配电网中分布式能源的紧密监控和控制。

英文摘要:

There is an increasing need for monitoring and controlling uncertainties brought by distributed energy resources in distribution grids. For such goal, accurate multi-phase topology is the basis for correlating measurements in unbalanced distribution networks. Unfortunately, such topology knowledge is often unavailable due to limited investment, especially for \revv{low-voltage} distribution grids. Also, the bus phase labeling information is inaccurate due to human errors or outdated records. For this challenge, this paper utilizes smart meter data for an information-theoretic approach to learn the topology of distribution grids. Specifically, multi-phase unbalanced systems are converted into symmetrical components, namely positive, negative, and zero sequences. Then, this paper proves that the Chow-Liu algorithm finds the topology by utilizing power flow equations and the conditional independence relationships implied by the radial multi-phase structure of distribution grids with the presence of incorrect bus phase labels. At last, by utilizing Carson's equation, this paper proves that the bus phase connection can be correctly identified using voltage measurements. For validation, IEEE systems are simulated using three real data sets. The simulation results demonstrate that the algorithm is highly accurate for finding multi-phase topology even with strong load unbalancing condition and DERs. This ensures close monitoring and controlling DERs in distribution grids.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑