arXivDaily arXiv每日学术速递 周一至周五更新
感恩节,周五至周末无更新,大家顺遂。周一再来吧
arXiv 2607.03324eess.SYcs.AIcs.SY
收藏

配电系统中用于碳感知人工智能数据中心的分层多智能体强化学习

Hierarchical Multi-Agent Reinforcement Learning for Carbon-Aware AI Data Centers in Power Distribution Systems

LG Electronics(LG电子);Department of Electrical and Computer Engineering(电气电子工程系);School of Electrical and Electronics Engineering(电气电子工程学院)

Hyunsoo Lee, Panggah Prabawa, Dae-Hyun Choi, Joongheon Kim

AI总结:

针对人工智能数据中心能耗致碳排放增加问题,提出分层碳感知多智能体强化学习框架,含工作负载管理器和本地数据中心智能体,利用数据和碳强度分配任务、调度运行,在IEEE 33节点系统评估其有效性。

摘要:

由于人工智能应用的快速扩展,人工智能数据中心(AIDC)能源消耗导致的碳排放显著增加,因此人工智能数据中心的环保能源管理至关重要。本文提出了一种分层碳感知多智能体强化学习(CA-MARL)框架,用于在不确定性下实现AIDC的稳健高效运行,同时确保配电系统的低碳运行。该框架包括一个工作负载管理器(WM)智能体和多个使用多智能体变压器方法训练的本地AIDC智能体,分别对应于一个全局AIDC聚合器和一个本地AIDC运营商。利用AIDC运行数据以及从碳排放流集成配电系统运营商问题计算出的节点碳强度(NCI),WM智能体在所有AIDC之间进行人工智能训练和推理作业的空间分配。基于从WM智能体分配的作业和NCI信息,每个AIDC智能体通过执行以下任务来调度AIDC的经济和环保运行:i)训练作业的时间转移,ii)AIDC内训练图形处理单元(GPU)块和推理GPU的空间分配,以及iii)冷却系统送风温度的控制。使用IEEE 33节点配电系统评估了所提出框架的有效性。

英文摘要:

Eco-friendly energy management for artificial intelligence data centers (AIDCs) is crucial because of the significant increase in energy consumption-induced carbon emissions from AIDCs resulting from the rapid expansion of AI applications. This paper proposes a hierarchical carbon-aware multi-agent reinforcement learning (CA-MARL) framework for robust and efficient operations of AIDCs under uncertainties while ensuring low-carbon operation of power distribution systems. The framework comprises a workload manager (WM) agent and multiple local AIDC agents trained using a multi-agent transformer method, corresponding to a global AIDC aggregator and a local AIDC operator, respectively. Leveraging AIDC operation data along with nodal carbon intensity (NCI) calculated from the carbon emission flow-integrated distribution system operator problem, the WM agent spatially allocates AI training and inference jobs among all AIDCs. Based on the jobs allocated from the WM agent and NCI information, each AIDC agent schedules economical and eco-friendly operations of the AIDC by performing the following tasks: i) temporal shifting of training jobs, ii) spatial allocation of training graphics processing unit (GPU) blocks and inference GPUs within the AIDC, and iii) control of the supply air temperature of the cooling system. The effectiveness of the proposed framework was assessed using an IEEE 33-node power distribution system.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑