人工智能时代美国超大规模数据中心隐藏的水地理情况
The Hidden Water Geography of U.S. Hyperscale Data Centers in the AI Era
AI总结:
研究美国超大规模数据中心用水路径,通过关联设施位置与电力区域等数据绘制472个设施的两种用水路径图,明确不同路径热点地理分布及占比,指出决策重点。
摘要:
数据中心的用水通常作为单一足迹报告,但水通过冷却和发电电力系统这两个物理上不同的途径消耗。我们通过将设施位置与电力区域、水文盆地和水资源压力数据联系起来,绘制了美国472个超大规模设施的这两种途径。在基线假设下,运营用水量总计约300 GL yr^-1,与电力相关的水占总量的四分之三。两条路径产生不同的热点地理分布……
英文摘要:
Water use by data centers is routinely reported as a single footprint, but water is consumed through two physically distinct pathways: at the site for cooling and in the power system that generates electricity. We mapped both pathways for 472 U.S. hyperscale facilities by linking facility locations to electricity regions, hydrologic basins, and water-stress data. Under baseline assumptions, operational water consumption totals approximately 300 GL yr^-1 (range 205-451 across scenarios), with electricity-related water contributing three-quarters of the total. The two pathways produce different hotspot geographies: direct cooling burdens concentrate in stressed western and south-central basins, whereas electricity-related burdens concentrate in a few eastern grid regions with fossil-heavy supply. Just 3 of 24 hosting balancing authorities account for 59% of electricity-related water. Separating pathways identifies which decisions matter where: cooling design and water sourcing locally, electricity planning and procurement regionally
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。