基于几何驱动的构网型逆变器孤岛检测与故障分类:基于法向双曲不变流形与物理导出阈值的框架
Geometry-Driven Islanding Detection and Fault Classification for Grid-Forming Inverters: A Normally Hyperbolic Invariant Manifold Framework with Physics-Derived Thresholds
AI总结:
提出一种基于法向双曲不变流形和随机假设检验的构网型逆变器孤岛检测与故障分类框架,通过协方差矩阵和卡方分布实现无调参阈值,并满足IEEE 1547-2018标准。
摘要:
本文提出了一种基于法向双曲不变流形(NAIM)和随机假设检验的几何驱动检测与故障分类框架,用于构网型(GFM)逆变器。GFM下垂流形$\mathcal{M}_0$被识别为闭环动力学的NAIM。电网噪声下的横向波动被建模为Ornstein-Uhlenbeck过程,长期协方差通过代数Lyapunov方程获得。检测统计量$D_t=T_w\bar{\xi}_{\perp}^{\top}\Sigma_{\mathrm{long}}^{-1}\bar{\xi}_{\perp}$在原假设下收敛于$\chi^2(2)$,从而得到无调参阈值$D_\alpha=-2\ln\alpha$和渐近精确的虚警率$\alpha$。纠正了早期公式中的两倍误差,并通过9种窗口长度和3个显著性水平下的8000次蒙特卡洛实现进行了验证。Berry-Esseen界$d_{\mathrm{KS}}\leq1.6704/(\beta T_w)$得到了经验证实。最小窗口条件$T_w\geq10/\beta_{\min}\approx1.0$ s(其中$\beta_{\min}=\min(\omega_f,\omega_v)$)满足IEEE 1547-2018的两秒检测要求。一个协同设计定理表明,同时增加$(\omega_f,\omega_v)$会扩大Fenichel谱间隙、收紧原假设协方差并降低虚警率。模态分解分离了频率和电压贡献,使得无需额外传感器即可对孤岛和电压故障进行分类。案例研究证实了正常运行的正确接受、软孤岛的快速检测以及10%电压暂降的准确识别。
英文摘要:
This paper presents a geometry-driven detection and fault-classification framework for grid-forming (GFM) inverters based on normally hyperbolic invariant manifolds (NAIM) and stochastic hypothesis testing. The GFM droop manifold $\mathcal{M}_0$ is identified as a NAIM of the closed-loop dynamics. Transverse fluctuations under grid noise are modeled as an Ornstein--Uhlenbeck process, and the long-run covariance is obtained from the algebraic Lyapunov equation. The detection statistic $D_t=T_w\barξ_{\perp}^{\top}Σ_{\mathrm{long}}^{-1}\barξ_{\perp}$ converges to $χ^2(2)$ under the null hypothesis, yielding the tuning-free threshold $D_α=-2\lnα$ and an asymptotically exact false-alarm rate $α$. A factor-of-2 error in earlier formulations is corrected and validated using 8,000 Monte Carlo realizations over nine window lengths and three significance levels. The Berry--Esseen bound $d_{\mathrm{KS}}\leq1.6704/(βT_w)$ is confirmed empirically. The minimum window condition $T_w\geq10/β_{\min}\approx1.0$ s, where $β_{\min}=\min(ω_f,ω_v)$, satisfies the IEEE 1547-2018 two-second detection requirement. A co-design theorem shows that increasing $(ω_f,ω_v)$ simultaneously enlarges the Fenichel spectral gap, tightens the null covariance, and reduces the false-alarm rate. Modal decomposition separates frequency and voltage contributions, enabling classification of islanding and voltage faults without additional sensors. Case studies confirm correct acceptance of normal operation, rapid detection of soft islanding, and accurate identification of a 10\% voltage sag.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。