基于混合储能系统和残差可微预测控制的AI数据中心功率波动源侧缓解

Source Side Mitigation of AI Datacenter Power Fluctuations with a Hybrid Energy Storage System and Residual Differentiable Predictive Control

James Watt School of Engineering, University of Glasgow(格拉斯哥大学詹姆斯·瓦特工程学院);College of Information and Electrical Engineering, China Agricultural University(中国农业大学信息与电气工程学院)

Haiyang You, Chengwei Lou, Jin Yang

AI总结:

针对AI数据中心工作负载引起的功率波动,提出混合储能系统与可微预测控制框架(HESS-DPC),通过离线训练残差可微预测策略修正规则基线,在NPCC 140节点系统上实现电网侧残余偏差降低,发电机峰峰频率偏差减少80%以上。

摘要:

超大规模AI数据中心的快速增长在互联点引入了结构化的、由工作负载驱动的有功功率波动。这些波动对电网表现为时变扰动注入,无法通过传统的峰值或平均负荷表示来捕捉。为了在残余功率扰动传播到大电网之前减少它,本文提出了一种混合储能系统与可微预测控制(HESS-DPC)框架,用于数据中心侧的功率平滑。首先建立了一个工作负载驱动的扰动模型,将互联点负荷偏差表示为训练和微调工作负载的叠加,以捕捉可能激发发电机频率动态的结构化强迫输入。然后,一个基于频率的规则控制器将该偏差分配给电池储能系统(BESS)和超级电容器(SC),将能量主导分量分配给BESS,将快速变化分量分配给SC。为了克服固定频率分解的预测和约束限制,离线训练了一个残差可微预测控制策略,以在规则基线周围计算有限时域的命令修正,同时强制执行一步安全保护。在NPCC 140节点系统上的仿真表明,HESS-DPC在工作负载转换期间减少了电网侧残余偏差,改善了SC荷电状态在长时间运行中的可持续性,并将所有监测发电机的峰峰频率偏差降低了80%以上,受影响最严重的发电机响应从15.1 mHz降至1.3 mHz。这些结果证实,在数据中心互联点进行本地有功功率平滑可以显著减轻由AI工作负载引起的频率扰动。

英文摘要:

The rapid growth of hyperscale AI datacenters introduces structured, workload-driven active-power fluctuations at the point of interconnection. These fluctuations appear to the grid as time-varying disturbance injections that cannot be captured by conventional peak- or average-load representations. To reduce the residual power disturbance before it propagates into the bulk power system, this paper proposes a hybrid energy storage system with differentiable predictive control (HESS-DPC) framework for datacenter-side power smoothing. A workload-driven disturbance model is first established, representing the point-of-interconnection load deviation as the superposition of training and fine-tuning workloads to capture the structured forcing inputs that can excite generator frequency dynamics. A frequency-based rule-based controller then allocates this deviation between a battery energy storage system (BESS) and a supercapacitor (SC), assigning the energy-dominant component to the BESS and the fast-varying component to the SC. To overcome the anticipation and constraint limitations of fixed-frequency decomposition, a residual differentiable predictive control policy is trained offline to compute finite-horizon command corrections around the rule-based baseline while enforcing a one-step safeguard. Simulations on the NPCC 140-bus system show that HESS-DPC reduces grid-side residual deviations during workload transitions, improves SC state-of-charge sustainability over extended operation, and reduces generator peak-to-peak frequency deviations by more than 80 percent across all monitored generators, with the worst-affected generator response falling from 15.1 mHz to 1.3 mHz. These results confirm that local active-power smoothing at the datacenter point of interconnection can substantially mitigate frequency disturbances caused by AI workloads.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑