通过基于EWMA-RTTA的二次外推实现集成输配电网中准确的频率响应建模
Accurate Frequency Response Modeling in Integrated T&D Co-Simulation via EWMA-RTTA-Based Quadratic Extrapolation
AI总结:
本文提出基于EWMA-RTTA的二次外推方法,用于解决异步仿真环境中输配电网频率建模的准确性问题,通过改进电压和相角预测提升了频率估计精度,实验结果表明其在IBR频率响应建模中具有更高的准确性。
摘要:
逆变器基于资源(IBRs)特别是分布式光伏(DPVs)的大规模集成进入配电网增加了对集成输配电网(T&D)联合仿真的需求。此类联合仿真的关键挑战在于准确地在两个异步仿真环境中建模系统频率。例如,传输系统在相量域中模拟,可以使用10毫秒的仿真时间步长,而配电网系统在电磁瞬态域(EMT)中模拟以包含IBR模型,使用更细的100微秒时间步长。为了确保配电网系统中基于锁相环(PLL)的频率估计准确,必须在10毫秒传输间隔内预测电压幅值和相角变化,而不是使用恒定值导致不准确的频率计算。当建模由IBRs提供的初级和次级频率响应服务时,这个问题变得尤为关键。为了解决这一挑战,我们提出了一种自动的指数加权移动平均实时阈值适应(EWMA-RTTA)方法,该方法利用二次外推来更精确地预测电压幅值和相角趋势。所提出的方法通过两种Opal-RT仿真器进行验证:一个模拟IEEE 118节点传输系统,另一个模拟IEEE 123节点配电网。仿真结果表明,与不考虑时间不匹配的方法相比,我们的方法将归一化平均绝对误差(nMAE)提高了25.7倍,提供了一种可扩展且准确的现代电力系统中IBR频率响应建模解决方案。
英文摘要:
The large-scale integration of inverter-based resources (IBRs), particularly distributed photovoltaics (DPVs), into distribution networks increases the need for integrated transmission and distribution (T&D) co-simulation. A key challenge in such co-simulation lies in accurately modeling system frequency across two asynchronous simulation environments. For example, the transmission system, simulated in the phasor domain, can operate with a simulation timestep of 10 ms, while the distribution system, simulated in the electromagnetic transient domain (EMT) to include IBR models, uses a much finer timestep of 100 microseconds. To ensure accurate PLL-based frequency estimation in distribution systems, it is essential to predict voltage magnitude and phase angle variations within the 10 ms transmission intervals, rather than using constant values that cause inaccurate frequency calculations. This issue becomes particularly critical when modeling primary and secondary frequency response services provided by IBRs. To address this challenge, we propose an automated Exponentially Weighted Moving Average Real-Time Threshold Adaptation (EWMA-RTTA) method, which utilizes Quadratic Extrapolation to predict voltage magnitude and phase angle trends more precisely. The proposed method is validated using two Opal-RT simulators: one simulating an IEEE 118-bus transmission system and the other simulating an IEEE 123-bus distribution network. Simulation results demonstrate that our approach improves the normalized mean absolute error (nMAE) by a factor of 25.7 compared to methods that do not account for time mismatches, offering a scalable and accurate solution for modeling IBR-based frequency response in modern power systems.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。