arXiv 2511.07553eess.SYcs.SY
收藏

面向频率的稀疏优化用于诊断电网不稳定性与崩溃

Frequency-Aware Sparse Optimization for Diagnosing Grid Instabilities and Collapses

University at Buffalo–SUNY(纽约州立大学布法罗分校);New York Power Authority(纽约电力局);GE Vernova Advanced Research(GE Vernova先进研究院);University of Vermont(佛蒙特大学)

Swadesh Vhakta, Denis Osipov, Reetam Sen Biswas, Amritanshu Pandey, Seyyedali Hosseinalipour, Shimiao Li

AI总结:

本文提出一种面向频率的稀疏优化方法,用于从稳态角度主动诊断和管理频率不稳定性风险,通过识别关键脆弱性源来确保系统稳定。

摘要:

本文旨在从稳态角度主动诊断和管理频率不稳定性风险,而无需依赖导数依赖的暂态建模。具体而言,我们共同解决两个问题(Q1)生存性:在扰动后及随后的初级频率响应后,系统能否进入健康的稳态(可行的频率偏差Δf可接受)?(Q2)主导脆弱性:如果发现不稳定,哪些关键脆弱性导致不稳定和/或完全崩溃?为了解决这些问题,我们首先将稳态功率流状态扩展以包含频率依赖的调速器关系(即调速器功率流)。随后,我们提出了一种面向频率的稀疏优化,寻找最小的节点位置集,包含可测量的补偿(纠正措施)以确保功率平衡并维持频率在预定义/可接受的范围内。我们在标准传输系统上评估了我们的方法,以实证验证其定位主导脆弱源的能力。对于一个1354节点的大型系统,我们的方法在N-1发电量中断(3424.8 MW)的情况下,仅检测到四个节点的补偿,同时 enforcing 最大允许的稳态频率下降为0.06 Hz(否则频率下降近0.08 Hz)。我们进一步验证了该方法的可扩展性,要求在1354节点系统中获得稀疏解的时间不到四分钟。

英文摘要:

This paper aims to proactively diagnose and manage frequency instability risks from a steady-state perspective, without the need for derivative-dependent transient modeling. Specifically, we jointly address two questions (Q1) Survivability: following a disturbance and the subsequent primary frequency response, can the system settle into a healthy steady state (feasible with an acceptable frequency deviation $Δf$)? (Q2) Dominant Vulnerability: if found unstable, what critical vulnerabilities create instability and/or full collapse? To address these questions, we first augment steady-state power flow states to include frequency-dependent governor relationships (i.e., governor power flow). Afterwards, we propose a frequency-aware sparse optimization that finds the minimal set of bus locations with measurable compensations (corrective actions) to enforce power balance and maintain frequency within predefined/acceptable bounds. We evaluate our method on standard transmission systems to empirically validate its ability to localize dominant sources of vulnerabilities. For a 1354-bus large system, our method detects compensations to only four buses under N-1 generation outage (3424.8 MW) while enforcing a maximum allowable steady-state frequency drop of 0.06 Hz (otherwise, frequency drops by nearly 0.08 Hz). We further validate the scalability of our method, requiring less than four minutes to obtain sparse solutions for the 1354-bus system.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑