arXivDaily arXiv每日学术速递 周一至周五更新
arXiv周末暂无论文更新,休息一下吧,周末愉快~~
arXiv 2511.00296eess.SYcs.SY
收藏

通过单位启停模型分析需求响应对短路电流的影响

Analyzing the Impact of Demand Response on Short-Circuit Current via a Unit Commitment Model

Technical University of Madrid(马德里理工大学);Aalto University(阿尔托大学)

Peng Wang, Zhengmao Li, Luis Badesa

AI总结:

本文通过单位启停模型研究需求响应对短路电流的影响,发现DR可降低总成本但可能影响SCC水平,合理协调灵活负载可有效平衡成本与稳定性。

摘要:

在低碳电网中,通过需求响应(DR)等机制可以增强系统灵活性,从而提高可再生能源的利用效率。然而,随着同步发电机(SGs)被具有逆变器基于资源(IBR)特性的可再生能源取代,系统稳定性受到严重影响。由于IBRs的过载能力有限,其短路电流(SCC)贡献远小于SGs。因此,保护设备可能在故障时无法跳闸。 Consequently,剩余的SGs在提供足够的SCC方面起着关键作用。由于SGs的启停与系统负荷条件密切相关,DR可以间接影响其SCC供应,这种关系在文献中尚未被研究。因此,本文将DR和SCC约束纳入单位启停问题,并在IEEE 30节点系统上进行了案例研究。结果表明,尽管DR可以通过调整电力需求来减少总成本,但它可能导致SCC水平不足。然而,当灵活负载与SCC需求得到适当协调时,总成本仅增加0.3%,这显著低于无DR的系统调度成本。这证明了DR可以在成本效益方面促进稳定系统的运行。

英文摘要:

In low-carbon grids, system flexibility can be enhanced through mechanisms such as Demand Response (DR), enabling the efficient utilization of renewable energy. However, as Synchronous Generators (SGs) are being replaced by renewable energy sources characterized by Inverter-Based Resources (IBR), system stability is severely affected. Due to the limited overload capability of IBRs, their Short-Circuit Current (SCC) contribution is much smaller than that of SGs. As a result, protection devices may fail to trip during faults. Consequently, the remaining SGs play a key role in providing sufficient SCC. Since the commitment of SGs is closely related to system loading conditions, DR can indirectly affect their SCC provision, a relationship that has not yet been investigated in the literature. Therefore, this paper incorporates both DR and SCC constraints into a unit commitment problem and conducts case studies on an IEEE 30-bus system. The results show that although DR can reduce total costs by adjusting power demand, it may also lead to inadequate SCC levels. Nevertheless, when flexible loads are properly coordinated with SCC requirements, the total cost increases by only 0.3%, which is significantly lower than the cost of system dispatch without DR. This demonstrates that DR can facilitate stable system operation in a cost-effective manner.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑