主动冷却装置:一种用于开发时空温度控制策略的柔性实验室规模实验单元

Active Cooling Device: A Flexible, Lab-Scale Experimental Unit to Develop Spatio-Temporal Temperature Control Strategies

National Research Council Canada(加拿大国家研究委员会)

Victor Oliveira Ferreira, Wiebke Mainville, Vincent Raymond, Jean-Michel Lamarre, Antoine Hamel, Mikael Vaillant, Moncef Chioua, Bruno Blais

AI总结:

本研究提出一种实现多输入多输出歧管热管理技术的柔性实验室规模主动冷却实验单元,提供全套设计文件、组装指南与使用示例,可用于定制时空温度控制策略的性能评估。

摘要:

我们提出了一种实验单元,用于实现Lamarre与Raymond(2023)提出的“多输入多输出歧管”热管理技术。该装置可用于旨在控制时空温度分布的实验,通过冲击冷却液射流,借助对准目标表面的通道歧管实现温度控制。流体方向通过切换通道的角色(输入、输出或关闭)来控制。本工作相关文件包括计算机辅助设计(CAD)STEP文件、用于制造印刷电路板(PCB)的Gerber文件,以及用Python编写的图形用户界面(GUI)。我们提供了组装该实验装置的分步指南,还介绍了通过GUI与装置交互的操作说明,GUI可实时跟踪样品温度和每个流量控制装置的流速。此外,我们还提供了装置的使用示例,包括阶跃响应的系统表征、比例-积分-微分(PID)性能跟踪,以及耦合系统中的扰动抑制。通过本工作相关开放仓库中提供的文件,可便捷扩展其应用场景。该主动冷却装置具备安全、灵活、设计完整的特点,可用于在实验室规模下评估采用封闭冲击射流定制温度控制策略的性能。

英文摘要:

We present an experimental unit that realizes the ``multi-input, multi-output manifold'' thermal management technology proposed by Lamarre & Raymond (2023). The proposed setup can be used for experiments aimed at controlling spatiotemporal temperature distribution. Temperature control is achieved by impinging coolant fluid jets, leveraging a manifold of channels targeted to the surface. The direction of the fluid is controlled by shifting the role of channels between inputs, outputs, or closing them. Files associated with this work include Computer-Aided Design (CAD) STEP files, Gerber files to manufacture a Printed Circuit Board (PCB), and a Graphical User Interface (GUI) written in Python. We provide a step-by-step guide to assemble the experimental setup. We also provide instructions to interact with the setup through the GUI, which allows for real-time tracking of sample temperature and flow rates per flow control device. Additionally, we provide examples of usage of the setup, including system characterization with step response, Proportional-Integral-Derivative performance tracking, and disturbance rejection in a coupled system. Extending the application is accessible through the files provided in the open repository associated with this work. The active cooling device presents a safe, flexible, and complete design, allowing for lab-scale assessment of the performance of custom temperature control strategies using enclosed impinging jets.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑