在机组组合问题中实现通用阶次频率动态响应模型与频率偏移持续时间判据

Implementing General-Order Frequency Dynamic Response Model and Frequency Excursion Duration Criterion in Unit Commitment Problem

Mohammad Rajabdorri, Bo Zhou, Lukas Sigrist, Enrique Lobato

AI总结:

针对传统含频率约束机组组合模型精度不足的问题,提出基于二阶动力学与Bernstein多项式逼近的MILP模型,新增频率偏移持续时间约束,经西班牙岛屿系统验证可在成本适度增加下提升频率安全性,适用于低惯量小规模电力系统。

摘要:

本文提出一种将频率动态特性纳入机组组合(UC)问题的新方法,采用通用阶次微分方程模型,并通过Bernstein多项式逼近求解。传统含频率约束的机组组合(FCUC)模型通常依赖简化的一阶假设或频率最低点等标量频率指标,间接强制满足动态行为要求。与之不同,我们的公式采用二阶动力学显式建模时域频率响应,能够更准确、灵活地刻画发电机行为。所得微分方程可通过Bernstein多项式实现高保真逼近,最终构建出混合整数线性规划(MILP)公式,在小规模电力系统中仍具备计算可处理性。\n此外,受继电器动作、设备保护等实际问题驱动,我们提出了一种基于频率偏移低于临界阈值的持续时间的新型约束。采用数据驱动方法,将阈值下方的面积(通过Bernstein逼近的积分计算)与频率偏差持续时间建立关联。所提框架利用西班牙某岛屿系统的真实数据完成验证,结果表明其在适度提升运行成本的同时增强了频率安全性。这些结果显示该方法在低惯量小规模电力系统中具备良好的应用潜力。

英文摘要:

This paper introduces a novel approach for incorporating frequency dynamics into the unit commitment (UC) problem through a general-order differential equation model, solved using Bernstein polynomial approximation. Traditional frequency-constrained UC (FCUC) models typically rely on simplified first-order assumptions or scalar frequency metrics, such as frequency nadir, to indirectly enforce dynamic behavior. In contrast, our formulation explicitly models time-domain frequency response using second-order dynamics, enabling a more accurate and flexible representation of generator behavior. The resulting differential equations are approximated with high fidelity using Bernstein polynomials, leading to a mixed-integer linear programming (MILP) formulation that remains computationally tractable for small-scale power systems. Additionally, we introduce a new constraint based on the duration of frequency excursions below a critical threshold, motivated by practical concerns such as relay operation and equipment protection. A data-driven method is employed to relate the area under this threshold-computed as the integral of the Bernstein approximation-to the duration of frequency deviation. The proposed framework is validated using real-world data from an island system in Spain, demonstrating enhanced frequency security with a moderate increase in operational cost. These results suggest the method's strong potential for application in low-inertia, small-scale power systems.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑