收藏

具有可变惯性的电网频率控制在线事件触发切换

Online Event-Triggered Switching for Frequency Control in Power Grids with Variable Inertia

UC San Diego(加州大学圣迭戈分校);University of Washington(华盛顿大学)

Jie Feng, Wenqi Cui, Jorge Cortés, Yuanyuan Shi

AI总结:

针对电网时变惯性导致频率动态退化的问题,提出一种基于Neural-PI控制器的在线事件触发切换算法,在保证系统稳定性的同时优化了时变惯性下的频率控制性能。

摘要:

可再生能源日益接入电网导致系统惯性时变,进而引起频率动态退化。缓解性能退化的可行方案是利用电力电子接口能源(如可再生能源发电机和电池储能)进行一次频率控制,通过调整其功率输出设定点以响应频率偏差。然而,在时变惯性下设计频率控制器具有挑战性。具体而言,为时不变系统设计的控制器应用于时变系统时,其稳定性或最优性可能受损。我们将时变惯性下的频率动态建模为非线性切换系统,其中各模式下的频率动态由非线性摇摆方程描述,不同模式代表不同惯性水平。我们识别出一种关键控制器结构,命名为Neural Proportional-Integral (Neural-PI) 控制器,可保证各模式的指数输入状态稳定性。为进一步提升性能,我们提出一种在线事件触发切换算法,从一组针对特定惯性水平优化的Neural-PI控制器中选择最合适的控制器。在IEEE 39节点系统上的仿真验证了所提在线切换控制方法在时变惯性下频率控制的有效性,兼具稳定性保证与优化性能。

英文摘要:

The increasing integration of renewable energy resources into power grids has led to time-varying system inertia and consequent degradation in frequency dynamics. A promising solution to alleviate performance degradation is using power electronics interfaced energy resources, such as renewable generators and battery energy storage for primary frequency control, by adjusting their power output set-points in response to frequency deviations. However, designing a frequency controller under time-varying inertia is challenging. Specifically, the stability or optimality of controllers designed for time-invariant systems can be compromised once applied to a time-varying system. We model the frequency dynamics under time-varying inertia as a nonlinear switching system, where the frequency dynamics under each mode are described by the nonlinear swing equations and different modes represent different inertia levels. We identify a key controller structure, named Neural Proportional-Integral (Neural-PI) controller, that guarantees exponential input-to-state stability for each mode. To further improve performance, we present an online event-triggered switching algorithm to select the most suitable controller from a set of Neural-PI controllers, each optimized for specific inertia levels. Simulations on the IEEE 39-bus system validate the effectiveness of the proposed online switching control method with stability guarantees and optimized performance for frequency control under time-varying inertia.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑