arXiv 2406.18514eess.SYcs.SY
收藏

大型交流电力系统直流分段后区域内部振荡与频率稳定性的解决

Addressing intra-area oscillations and frequency stability after DC segmentation of a large AC power system

Mathieu Robin, Javier Renedo, Juan Carlos Gonzalez-Torres, Aurelio Garcia-Cerrada, Luis Rouco, Abdelkrim Benchaib, Pablo Garcia-Gonzalez

AI总结:

针对大型交流电网直流分段后区域内部振荡和频率稳定性恶化的问题,提出在VSC-HVDC换流站配置有功和无功附加控制器以抑制振荡并提供频率支持,并在Nordic 44系统验证了其有效性。

摘要:

在过去几十年中,各种事件表明机电振荡是大型互联交流(AC)电力系统的主要隐患。利用高压直流输电(HVDC)系统对交流电力系统进行分段(简称直流分段)是一种将大型交流电网转化为由HVDC线路连接的多个异步交流集群的方法。这是缓解机电振荡及其他问题的一种极具前景的解决方案。具体而言,合理布置的直流分段能够消除选定的区域间机电振荡模式。然而,若缺乏附加控制器,直流分段将无法对剩余交流集群内的区域内部振荡模式提供阻尼,并且会恶化电力系统的频率稳定性。本文旨在填补这一空白,提出采用基于电压源换流器的HVDC(VSC-HVDC)系统进行直流分段,并在换流站配置附加控制器:(a) 用于异步交流集群间频率支持的有功功率附加控制器,以及 (b) 用于功率振荡阻尼(POD-Q)的无功功率附加控制器,以抑制区域内部振荡模式。本文将介绍所提出的附加控制器及其设计,并通过非线性和时域仿真与小信号稳定分析,在采用直流分段的 Nordic 44 测试系统上验证其有效性。

英文摘要:

In the last decades, various events have shown that electromechanical oscillations are a major concern for large interconnected Alternating Current (AC) power systems. Segmentation of AC power systems with High Voltage Direct Current (HVDC) systems (DC segmentation, for short) is a method that consists in turning large AC grids into a set of asynchronous AC clusters linked by HVDC links. It is a promising solution to mitigate electromechanical oscillations and other issues. In particular, an appropriately placed DC segmentation can stop a selected inter-area electromechanical oscillation mode. However, without supplementary controllers, DC segmentation will not contribute to the damping of the intra-area oscillation modes in the remaining AC clusters and will deteriorate the frequency stability of the power system. This paper aims at filling this gap and proposes the use of DC segmentation with HVDC systems based on Voltage Source Converters (VSC-HVDC) with supplementary controllers in the converter stations: (a) active-power supplementary controllers for frequency support among the asynchronous AC clusters and (b) a reactive-power supplementary controllers for Power Oscillation Damping (POD-Q), in order to damp the intra-area oscillation modes. The proposed supplementary controllers and their design will be presented, and their efficiency will be demonstrated on the Nordic 44 test system with DC segmentation by means of non-linear time-domain simulation and small-signal stability analysis.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑