评估建筑部门改造在冬季风暴Uri期间缓解ERCOT电力短缺的潜力
Assessing the Potential for Building Sector Retrofits to Mitigate ERCOT Electricity Shortfalls During Winter Storm Uri
AI总结:
该研究模拟ERCOT建筑能效与电气化改造在冬季风暴Uri期间的影响,发现单纯热泵电气化会加剧极端寒冷时段峰值负荷与短缺,而结合能效改造可显著缓解电力短缺并降低年用电。
摘要:
本分析调查了冬季风暴Uri期间,得克萨斯州电力可靠性委员会(ERCOT)住宅和商业建筑部门的能源表现。研究对ERCOT基准建筑存量,以及分别加装能效升级包、电气化升级包和能效+电气化升级包后的基准建筑存量进行了ERCOT电力需求建模。为建筑加装空气源热泵(ASHPs)的电气化情景,在一年中的每一天本都会相对于基准情景降低ERCOT日峰值电力需求,但冬季风暴Uri所在的那一周除外。当平均室外温度降至-5°C(23°F)以下时,ASHP效率下降会导致电气化情景需求超过基准情景在2月15日和16日两个不同的日需求峰值(87.3 GW和88.7 GW),达到111.8 GW和117.5 GW。能效升级包在这些日期会将日峰值需求降至67.0 GW和68.0 GW。能效+电气化升级包会将这些日期的峰值需求降至81.5 GW和85.6 GW。通过将建模电力需求与风暴期间ERCOT实际发电量进行比较生成电力短缺曲线后,结果表明,电气化情景的电力短缺(1741 GWh)会大于基准情景(1225 GWh),而能效情景(347 GWh)和能效+电气化情景(704 GWh)的电力短缺会低于基准情景。由于建筑制冷效率的提高,能效、电气化和能效+电气化情景均会降低夏季日峰值需求,并分别使年电力消耗降低5.9%、6.8%和11.9%。
英文摘要:
This analysis investigates energy performance of the residential and commercial building sectors in the Electric Reliability Council of Texas (ERCOT) during Winter Storm Uri. ERCOT electricity demand was modeled for the ERCOT baseline building stock as well as for the baseline building stock retrofitted with an efficiency upgrade package, an electrification upgrade package, and an efficiency + electrification upgrade package. The electrification scenario that retrofitted buildings with air-source heat pumps (ASHPs) would have lowered ERCOT daily peak electricity demand relative to the baseline scenario for every day of the year, except during the week of Winter Storm Uri. As the mean outdoor temperature dropped below -5°C (23°F), diminishing ASHP efficiency would have resulted in electrification scenario demand exceeding the two distinct baseline scenario daily demand peaks on February 15th and 16th (87.3 GW and 88.7 GW) to hit 111.8 GW and 117.5 GW. The efficiency package would have lowered daily peak demand on these days to 67.0 GW and 68.0 GW. The efficiency + electrification package would have lowered peak demand on these days to 81.5 GW and 85.6 GW. When electricity shortfall profiles were produced by comparing modeled electricity demand to actual ERCOT electricity generation during the storm, the results indicate that the electrification scenario electricity shortfall (1741 GWh) would have been larger than for the baseline scenario (1225 GWh) and the electricity shortfalls for the efficiency scenario (347 GWh) and efficiency + electrification scenario (704 GWh) would have been lower than the baseline. The efficiency, electrification, and efficiency + electrification scenarios would all have lowered summer daily peak demand due to improvements in building cooling efficiency and would have lowered annual electricity consumption by 5.9%, 6.8%, and 11.9%, respectively.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。