arXivDaily arXiv每日学术速递 周一至周五更新
arXiv 2311.01800eess.SYcs.SY
收藏

利用最少建筑信息与需求测量数据降低既有建筑供水温度的方法开发

Method development for lowering supply temperatures in existing buildings using minimal building information and demand measurement data

Jan Stock, Philipp Althaus, Sascha Johnen, André Xhonneux, Dirk Müller

AI总结:

本研究提出一种仅需有限数据的既有建筑供暖供水温度降低方法,通过LMTD法推导最低供热曲线,在德国多栋办公楼验证了其高效适用性并完成实际落地测试。

摘要:

在气候变化背景下,减少温室气体排放的必要性已广为人知。由于建筑供暖在主要依赖化石能源的总能耗中占比很高,提升供暖效率是极具前景的研究方向。降低建筑供暖系统的供水温度能为效率提升提供巨大潜力,因为热泵、区域供热等不同供热技术均可从低供水中获益。然而,目前大多数关于既有建筑可实现降温幅度的估算,都依赖房间级的可用测量数据,或是用于构建仿真模型的建筑物理特性详细信息。\n为挖掘多栋建筑的降温潜力并力求广泛适用性,本研究提出的方法聚焦于输入数据有限条件下的既有建筑降温估算。通过评估建筑级的历史热需求数据、室外温度以及已安装散热器的相关信息,采用对数平均温差(LMTD)方法计算出建筑内每台散热器实际所需的最低供水温度。基于不同室外温度下各房间计算得出的所需供水温度,确定需向整栋建筑供给的整体必要供水温度,进而推导出既有建筑可实现的最低供热曲线。\n该方法已应用于德国于利希研究中心园区内的多栋既有办公楼,证明其可在投入有限的情况下快速应用于多栋建筑。此外,研究还将开发的适配供热曲线在一栋实际建筑中落地实施,并与该供暖系统此前采用的供热曲线进行了对比评估。

英文摘要:

Regarding climate change, the need to reduce greenhouse gas emissions is well-known. As building heating contributes to a high share of total energy consumption, which relies mainly on fossil energy sources, improving heating efficiency is promising to consider. Lowering supply temperatures of the heating systems in buildings offers a huge potential for efficiency improvements since different heat supply technologies, such as heat pumps or district heating, benefit from low supply temperatures. However, most estimations of possible temperature reductions in existing buildings are based on available measurement data on room level or detailed building information about the building's physics to develop simulation models. To reveal the potential of temperature reduction for several buildings and strive for a wide applicability, the presented method focuses on estimations for temperature reduction in existing buildings with limited input data. By evaluating historic heat demand data on the building level, outdoor temperatures and information about installed heaters, the minimal actual necessary supply temperature is calculated for each heater in the building using the LMTD approach. Based on the calculated required supply temperatures for each room at different outdoor temperatures, the overall necessary supply temperatures to be provided to the building are chosen. Thus, the minimal heatcurve possible for an existing building is deduced. The method described is applied to multiple existing office buildings at the campus of Forschungszentrum Juelich, Germany, demonstrating the fast application for several buildings with limited expenditure. Furthermore, a developed adapted heatcurve is implemented in one real building and evaluated in relation to the previously applied heatcurve of the heating system.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑