配备同步调相机的海上风电场小信号稳定性与SCR增强
Small-Signal Stability and SCR Enhancement of Offshore WPPs with Synchronous Condensers
AI总结:
本文研究同步调相机对采用GFL和GFM控制的海上风电场的影响,通过状态空间模型评估小信号稳定性,并从数学和仿真验证其对整体稳定性及有效短路比(SCR)的增强作用。
摘要:
据报道,同步调相机能提高电力系统的整体稳定性和短路功率。出于同样原因,同步调相机也正被集成到海上风电场中。本文研究了同步调相机对采用电网跟随(GFL)和电网构建(GFM)变流器控制的海上风电场的影响。同步调相机的影响主要有两方面:(1)通过提供无功功率支持增强风电场的整体稳定性;(2)通过故障电流支持提升风电场的有效短路比(SCR)。因此,本文重点研究这些效应对并网风电场聚合模型的影响。为此,建立了测试系统的状态空间模型,以进行小信号稳定性评估并分析同步调相机对其稳定性的作用。此外,给出了同步调相机增强SCR的数学解释,并通过时域电磁暂态仿真进行了验证。
英文摘要:
Synchronous condensers (SCs) have been reported to improve the overall stability and short-circuit power of a power system. SCs are also being integrated into offshore wind power plants (WPPs) for the same reason. This paper, investigates the effect of synchronous condensers on an offshore wind power plant with grid-following (GFL) and grid-forming (GFM) converter controls. Primarily, the effect of synchronous condensers can be two-fold: (1) overall stability enhancement of the WPP by providing reactive power support, (2) contribution to the effective short circuit ratio (SCR) of the WPP by fault current support. Therefore, this paper focuses on studies concerning these effects on an aggregated model of a WPP connected to the grid. To that end, a state-space model of the test system is developed for small-signal stability assessment and the synchronous condenser's effect on its stability. In addition, a mathematical explanation of SCR enhancement with synchronous condenser is provided and is verified with time-domain electromagnetic transient simulations.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。