基于自回归系数的连接至3型风电场输电线路智能保护
Autoregressive Coefficients based Intelligent Protection of Transmission Lines Connected to Type-3 Wind Farms
AI总结:
本文针对连接DFIG风电场的输电线路保护误动问题,提出基于自回归系数、模糊推理和深度学习的智能保护方案,并在多种系统条件下验证了其有效性。
摘要:
对于连接至基于双馈感应发电机(DFIG)的大容量风电场(WFs)的输电线路,保护继电器可能发生误动作。本文研究了保护此类线路的距离继电器性能,并提出了一种基于统计模型的电网与风电场之间区域的智能保护方法。所提方法采用自适应模糊推理系统,基于三相电流的自回归(AR)系数来检测故障,这些系数通过最小冗余最大相关算法进行选择。深度学习网络用于监督故障检测、后续的故障定位和分类。该方案的有效性在IEEE 9节点和IEEE 39节点系统上进行了评估,考虑了不同的故障电阻、故障起始时间、故障位置、故障类型、风速和变压器连接方式。此外,在验证所提方案时,还考虑了以下因素的影响:4型风电场的存在、双回线路、风电场容量、电网强度、FACTS装置、永久性故障上的重合闸、功率摇摆、功率摇摆期间的故障、电压失稳、负荷侵入、高阻抗故障、发展性故障和跨区域故障、近端和远端故障、CT饱和、采样率、数据窗口大小、同步误差、噪声以及半监督学习。结果表明,所提方法在保护连接至风电场的输电线路时,能够有效应对各种系统条件和配置。
英文摘要:
Protective relays can mal-operate for transmission lines connected to doubly fed induction generator (DFIG) based large capacity wind farms (WFs). The performance of distance relays protecting such lines is investigated and a statistical model based intelligent protection of the area between the grid and the WF is proposed in this article. The suggested method employs an adaptive fuzzy inference system to detect faults based on autoregressive (AR) coefficients of the 3-phase currents selected using minimum redundancy maximum relevance algorithm. Deep learning networks are used to supervise the detection of faults, their subsequent localization, and classification. The effectiveness of the scheme is evaluated on IEEE 9-bus and IEEE 39-bus systems with varying fault resistances, fault inception times, locations, fault types, wind speeds, and transformer connections. Further, the impact of factors like the presence of type-4 WFs, double circuit lines, WF capacity, grid strength, FACTs devices, reclosing on permanent faults, power swings, fault during power swings, voltage instability, load encroachment, high impedance faults, evolving and cross-country faults, close-in and remote-end faults, CT saturation, sampling rate, data window size, synchronization error, noise, and semi-supervised learning are considered while validating the proposed scheme. The results show the efficacy of the suggested method in dealing with various system conditions and configurations while protecting the transmission lines that are connected to WFs.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。