arXivDaily arXiv每日学术速递 周一至周五更新
arXiv 2309.09073cs.LG
收藏

利用主动学习增强个性化热舒适模型以改进暖通空调控制

Enhancing personalised thermal comfort models with Active Learning for improved HVAC controls

Department of the Built Environment, National University of Singapore(新加坡国立大学建筑环境系)

Zeynep Duygu Tekler, Yue Lei, Xilei Dai, Adrian Chong

AI总结:

本文提出一种结合主动学习的个性化热舒适建模与 HVAC 控制框架,通过主动选择高信息量热条件进行标注,在减少 31.0% 标注工作量的同时实现 1.3% 节能提升和 98% 以上热满意度。

摘要:

开发个性化热舒适模型以指导建筑中的以 occupant 为中心的控制(OCC),需要收集大量实时的 occupant 偏好数据。在大规模实施中,这一过程可能具有高度侵入性且耗费大量人力,从而限制了现实世界中 OCC 实施的实用性。为解决这一问题,本研究提出了一种基于热偏好的暖通空调(HVAC)控制框架,并利用主动学习(Active Learning, AL)加以增强,以应对此类 OCC 系统在现实部署中面临的数据挑战。所提出的 AL 方法主动识别最具信息价值的热条件以供人工标注,并迭代更新有监督的热舒适模型。所得模型随后用于预测 occupant 在不同热条件下的热偏好,并将这些偏好集成到建筑的 HVAC 控制中。我们在一个真实测试平台的 EnergyPlus 仿真中,结合 58 名研究 occupant 的热偏好数据,验证了所提出的 AL 使能 OCC 的可行性。初步结果表明,与常规 OCC 相比,我们的 AL 使能 OCC 在整体标注工作量上显著减少(即 31.0%),同时仍实现了略微增加的节能效果(即 1.3%),并且热满意度保持在 98% 以上。这一结果表明,此类系统有潜力在未来现实部署中实现个性化舒适和节能的建筑运行。

英文摘要:

Developing personalised thermal comfort models to inform occupant-centric controls (OCC) in buildings requires collecting large amounts of real-time occupant preference data. This process can be highly intrusive and labour-intensive for large-scale implementations, limiting the practicality of real-world OCC implementations. To address this issue, this study proposes a thermal preference-based HVAC control framework enhanced with Active Learning (AL) to address the data challenges related to real-world implementations of such OCC systems. The proposed AL approach proactively identifies the most informative thermal conditions for human annotation and iteratively updates a supervised thermal comfort model. The resulting model is subsequently used to predict the occupants' thermal preferences under different thermal conditions, which are integrated into the building's HVAC controls. The feasibility of our proposed AL-enabled OCC was demonstrated in an EnergyPlus simulation of a real-world testbed supplemented with the thermal preference data of 58 study occupants. The preliminary results indicated a significant reduction in overall labelling effort (i.e., 31.0%) between our AL-enabled OCC and conventional OCC while still achieving a slight increase in energy savings (i.e., 1.3%) and thermal satisfaction levels above 98%. This result demonstrates the potential for deploying such systems in future real-world implementations, enabling personalised comfort and energy-efficient building operations.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑