arXivDaily arXiv每日学术速递 周一至周五更新
arXiv 2306.07772eess.SYcs.SY
收藏

迈向数字化运营的一步——一种用于超低温冷冻舱热动力学建模的新型灰箱方法

A step towards digital operations -- A novel grey-box approach for modelling the heat dynamics of Ultra-low temperature freezing chambers

Tao Huang, Peder Bacher, Jan Kloppenborg Møller, Francesco D'Ettorre, Wiebke Brix Markussen

AI总结:

针对超低温冷冻柜的智能监控与能耗管理需求,提出基于随机微分方程的灰箱热动力学建模方法,仅需常规运行的温度数据即可实现高精度预测,适配不同运行模式,提升了数字化应用的可行性。

摘要:

超低温(ULT)冷冻柜用于储存易腐生物样品,且能耗极高,这凸显了对可靠的智能监控与智慧能源管理方法的需求。本研究提出了一种基于随机微分方程的新型灰箱建模方法,用于描述ULT冷冻舱的热动力学特性。该建模方法仅需嵌入式传感器测得的温度数据,并利用常规运行时段的数据进行模型辨识。模型包含三个状态:舱体温度、围护结构温度以及局部蒸发器温度。研究特别关注局部蒸发器温度状态,将其建模为时变系统,以表征冷却强度的时间延迟和动态变化。研究对两台运行模式不同的ULT冷冻柜进行了建模,采用最大似然法估计未知的模型参数。结果表明,该模型能够准确预测控制探针测得的舱体温度(均方根误差RMSE<0.19°C),有望应用于未来状态预测。此外,局部蒸发器温度模型可有效适配不同的运行模式,并能反映局部冷却供应状态。该方法极大提升了ULT冷冻柜热动力学灰箱建模的实际可行性,可服务于多种潜在的数字化应用。该建模方法的一个主要局限是可辨识性较低,这一问题可通过基于参数相对变化推断模型参数来潜在解决。

英文摘要:

Ultra-low temperature (ULT) freezers store perishable bio-contents and have high energy consumption, which highlight a demand for reliable methods for intelligent surveillance and smart energy management. This study introduces a novel grey-box modelling approach based on stochastic differential equations to describe the heat dynamics of the ULT freezing chambers. The proposed modelling approach only requires temperature data measured by the embedded sensors and uses data from the regular operation periods for model identification. The model encompasses three states: chamber temperature, envelope temperature, and local evaporator temperature. Special attention is given to the local evaporator temperature state, which is modelled as a time-variant system, to characterize the time delay and dynamic variations in cooling intensity. Two ULT freezers with different operational patterns are modelled. The unknown model parameters are estimated using the maximum likelihood method. The results demonstrate that the models can accurately predict the chamber temperature measured by the control probe (RMSE < 0.19 °C) and are promising to be applied for forecasting future states. In addition, the model for local evaporator temperature can effectively adapt to different operational patterns and provide insight into the local cooling supply status. The proposed approach greatly promotes the practical feasibility of grey-box modelling of the heat dynamics for ULT freezers and can serve several potential digital applications. A major limitation of the modelling approach is the low identifiability, which can potentially be addressed by inferring model parameters based on relative parameter changes.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑