中大风条件下仓库建筑物内外火灾烟气扩散
Fire smoke dispersion inside and outside of a warehouse building in moderate and strong wind conditions
摘要:
在风力条件下,在位于城市地区的一个具有不同建筑风格的仓库中模拟了一场中等规模(8 MW)的火灾。本研究探讨邻近建筑物对风场的影响,以及对建筑物附近的防排烟性能和烟气扩散的影响。使用ANSYS Fluent CFD代码进行了25次CFD模拟,风速为5 m/s(中等)、10 m/s(强),每个风速为12个风向角(0 - 330 $^\circ$,30 $^\circ$增量),并以0 m/s作为参考。结果表明,建筑排烟系统的性能受风的影响较大,在中风速和强风风速下,排烟系统的性能分别达到参考质量流量的74%~ 114%和78%~ 158%。有趣的是,在许多情况下,通风机的排气流量增加,而不是受到风的阻碍。这是由于立面上入口和出口的布置以及墙壁和屋顶开口之间的压力差造成的。烟羽高度依赖于风的角度和建筑类型的上风和下风的火灾。观察到显著的城市峡谷效应和在高层建筑物后面形成的大漩涡,导致烟雾在离火灾很远的地方积聚。
英文摘要:
A moderate-sized (8 MW) fire was modeled in a warehouse located in an urban area with diverse architecture, under wind conditions. The study investigates the impact of neighboring architecture on the wind field and the resulting effect on smoke control performance and smoke dispersion in the vicinity of the building. 25 CFD simulations were performed using ANSYS Fluent CFD code, for wind velocities of 5 m/s (moderate), 10 m/s (strong) at 12 wind angles each (0 - 330$^\circ$, 30$^\circ$ increment), and at 0 m/s for reference. The results show that the performance of the building smoke venting system was impacted by the wind, reaching 74% - 114% and 78% - 158% of the reference mass flow at moderate and strong wind velocities, respectively. Interestingly, in multiple cases, the exhaust flow rate of the ventilators was increased rather than hindered by the wind. This was attributed to the arrangement of inlets and outlets on the facades and the resulting pressure difference between the wall and roof openings. The smoke plume was highly dependent on the wind angle and the type of architecture upwind and downwind of the fire. Significant urban canyon effects and large vortices forming behind tall buildings were observed, leading to smoke accumulation at a significant distance from the fire.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。