使用语法进化技术预测数据中心温度

Runtime data center temperature prediction using Grammatical Evolution techniques

Universidad Complutense de Madrid(马德里康普顿斯大学);Center for Computational Simulation(计算模拟中心);Universidad Politécnica de Madrid(马德里理工大学)

Marina Zapater, José L. Risco-Martín, Patricia Arroba, José L. Ayala, José M. Moya, Román Hermida

摘要:

数据中心是巨大的电力消费者,这既是因为计算所需的能源,也是因为将服务器保持在热红线以下所需的冷却。最常见的降低冷却成本的方法是提高数据室温度。然而,为了避免可靠性问题并提高能源效率,需要预测服务器在可变冷却设置下达到的温度。由于数据室复杂的热动力学,准确的运行时数据中心温度预测仍然是一个重要的挑战。通过使用Grammatical Evolution技术,本文提出了一种用于生成数据中心的温度模型以及在可变冷却设置下CPU和入口温度的运行时预测的方法。与耗时的计算流体动力学技术相反,我们的模型不需要关于问题的特定知识,可以在任意数据中心使用,如果条件发生变化,可以重新训练,并且在运行时预测期间的开销可以忽略不计。我们的模型已经通过使用真实数据中心场景的跟踪进行了训练和测试。我们的研究结果表明,我们可以完全预测的数据室中的服务器的温度,预测误差低于2 C和0.5 C的CPU和服务器的入口温度分别。

英文摘要:

Data Centers are huge power consumers, both because of the energy required for computation and the cooling needed to keep servers below thermal redlining. The most common technique to minimize cooling costs is increasing data room temperature. However, to avoid reliability issues, and to enhance energy efficiency, there is a need to predict the temperature attained by servers under variable cooling setups. Due to the complex thermal dynamics of data rooms, accurate runtime data center temperature prediction has remained as an important challenge. By using Gramatical Evolution techniques, this paper presents a methodology for the generation of temperature models for data centers and the runtime prediction of CPU and inlet temperature under variable cooling setups. As opposed to time costly Computational Fluid Dynamics techniques, our models do not need specific knowledge about the problem, can be used in arbitrary data centers, re-trained if conditions change and have negligible overhead during runtime prediction. Our models have been trained and tested by using traces from real Data Center scenarios. Our results show how we can fully predict the temperature of the servers in a data rooms, with prediction errors below 2 C and 0.5 C in CPU and server inlet temperature respectively.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑