基于模拟楼宇自动化系统传感器数据的非冷凝式锅炉故障检测
Fault Detection for Non-Condensing Boilers using Simulated Building Automation System Sensor Data
摘要:
建筑性能在试运行后会显著下降,导致能源消耗和相关温室气体排放增加。使用现有的传感器网络和物联网设备进行持续调试有可能通过不断识别系统退化和重新调整控制策略以适应实际建筑性能来最大限度地减少这种浪费。由于其对温室气体排放的重大贡献,用于建筑供暖的燃气锅炉系统的性能至关重要。回顾锅炉性能研究已被用来开发一套常见的故障和性能下降的条件下,已被集成到MATLAB/Simulink仿真器。这产生了一个标记数据集,其中包含14个非冷凝锅炉中每个锅炉的大约10,000个稳态性能模拟。所收集的数据用于训练和测试故障分类,使用K-最近邻,决策树,随机森林和支持向量机。结果表明,支持向量机方法给出了最好的预测精度,始终超过90%,和泛化跨多个锅炉是不可能的,由于低分类精度。
英文摘要:
Building performance has been shown to degrade significantly after commissioning, resulting in increased energy consumption and associated greenhouse gas emissions. Continuous Commissioning using existing sensor networks and IoT devices has the potential to minimize this waste by continually identifying system degradation and re-tuning control strategies to adapt to real building performance. Due to its significant contribution to greenhouse gas emissions, the performance of gas boiler systems for building heating is critical. A review of boiler performance studies has been used to develop a set of common faults and degraded performance conditions, which have been integrated into a MATLAB/Simulink emulator. This resulted in a labeled dataset with approximately 10,000 simulations of steady-state performance for each of 14 non-condensing boilers. The collected data is used for training and testing fault classification using K-nearest neighbour, Decision tree, Random Forest, and Support Vector Machines. The results show that the Support Vector Machines method gave the best prediction accuracy, consistently exceeding 90%, and generalization across multiple boilers is not possible due to low classification accuracy.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。