四线配电网中的最优潮流:公式构建与基准测试
Optimal Power Flow in Four-Wire Distribution Networks: Formulation and Benchmarking
AI总结:
针对低压四线配电网的三相不平衡特性,构建电流-电压和功率-电压两类变量空间的OPF公式并对比性能,量化Kron化简的建模误差与求解影响,明确电流-电压变量公式更具优势。
摘要:
近年来,配电网领域已提出多种应用场景,其中许多可建模为最优潮流(OPF)问题——这是一类包含电网稳态物理模型的数学优化问题。若电网负载平衡且线路换位,电网模型可简化为单相等效模型,但低压配电网不满足这些假设,因此电网模型需准确建模三相不平衡的影响。全球多数地区的低压配电网包含四根导线,即三相加中性线。本文针对此类电网,在电流-电压和功率-电压两类变量空间中构建了涵盖变压器、并联元件和电压依赖性负载的OPF公式,并对比了二者的鲁棒性和可扩展性。针对128个低压配电网的案例研究还量化了Kron化简(一种网络降阶方法)引入的建模误差及其对求解时间的影响。本研究凸显了四线网络中电流-电压变量公式相较于功率-电压变量公式的优势。
英文摘要:
In recent years, several applications have been proposed in the context of distribution networks. Many of these can be formulated as an optimal power flow problem, a mathematical optimization program which includes a model of the steady-state physics of the electricity network. If the network loading is balanced and the lines are transposed, the network model can be simplified to a single-phase equivalent model. However, these assumptions do not apply to low-voltage distribution networks, so the network model should model the effects of phase unbalance correctly. In many parts of the world, the low-voltage distribution network has four conductors, i.e. three phases and a neutral. This paper develops OPF formulations for such networks, including transformers, shunts and voltage-dependent loads, in two variable spaces, i.e. current-voltage and power-voltage, and compares them for robustness and scalability. A case study across 128 low-voltage networks also quantifies the modelling error introduced by Kron reductions and its impact on the solve time. This work highlights the advantages of formulations in current-voltage variables over power-voltage, for four-wire networks.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。