超市冷藏柜蒸发器阀门尺寸的估算

Estimation of Evaporator Valve Sizes in Supermarket Refrigeration Cabinets

Kenneth Leerbeck, Peder Bacher, Christian Heerup, Henrik Madsen

摘要:

在许多应用中,例如超市制冷系统的故障诊断和优化控制,重要的是确定机柜的热需求。这可以通过测量通过每个机柜的质量流量来容易地实现,然而,这是昂贵的并且在大规模部署中不可行。因此,重要的是能够从通常测量的监测数据估计瓣膜尺寸。阀门的尺寸是通过面积来测量的,面积可以用来计算通过阀门的质量流量--这个估计值被称为阀门常数。本文提出了一种估算蒸发器阀门常数的新方法。它被证明使用监测数据从一个制冷系统在超市组成的数据采样率为一分钟,但它表明,采样时间约为10-20分钟是足够的方法。通过对双级CO2制冷系统的热力学分析,建立了利用时间序列数据估算阀门常数的线性回归模型。线性回归要求数据中不存在瞬态动态,这取决于多个因素,例如采样时间。如果动态未建模,则可以通过残差的显著自相关来检测。为了在模型中包含动态,应用了具有外生变量的自回归移动平均模型(ARMAX),并展示了它如何有效地消除自相关,提供更无偏的估计,以及提高估计的准确性。此外,它表明,采样时间有一个巨大的影响阀估计。因此,介绍了一种选择最佳采样时间的方法。它通过探索每个蒸发器各自的频谱,为每个蒸发器单独工作。

英文摘要:

In many applications, e.g. fault diagnostics and optimized control of supermarket refrigeration systems, it is important to determine the heat demand of the cabinets. This can easily be achieved by measuring the mass flow through each cabinet, however, that is expensive and not feasible in large-scale deployments. Therefore it is important to be able to estimate the valve sizes from the monitoring data, which is typically measured. The valve size is measured by an area, which can be used to calculate mass flow through the valve -- this estimated value is referred to as the valve constant. A novel method for estimating the cabinet evaporator valve constants is proposed in the present paper. It is demonstrated using monitoring data from a refrigeration system in a supermarket consisting of data sampled at a one-minute sampling rate, however it is shown that a sampling time of around 10-20 minutes is adequate for the method. Through thermodynamic analysis of a two-stage CO2 refrigeration system, a linear regression model for estimating valve constants was developed using time series data. The linear regression requires that transient dynamics are not present in the data, which depends on multiple factors e.g. the sampling time. If dynamics are not modeled it can be detected by a significant auto-correlation of the residuals. In order to include the dynamics in the model, an Auto-Regressive Moving Average model with eXogenous variables (ARMAX) was applied, and it is shown how it effectively eliminates the auto-correlation and provides more unbiased estimates, as well as improved the accuracy estimates. Furthermore, it is shown that the sample time has a huge impact on the valve estimates. Thus, a method for selecting the optimal sampling time is introduced. It works individually for each of the evaporators, by exploring their respective frequency spectrum.

机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。

↑