On the Suitability of PLC Pulses for Power Line Fault Sensing via Time-Domain Reflectometry
摘要:
本文讨论了典型的电力线通信(PLC)脉冲通过脉冲压缩时域反射仪(TDR)在电力线故障检测的适用性。为此,我们首先仔细概述了TDR系统在配电网络上运行,讨论其局限性,并最终诉诸脉冲压缩程序。接下来,我们提出了封闭形式的表达式的脉冲和它们的自相关函数的典型PLC调制方案,即厄米对称正交频分复用(HS-OFDM),脉冲超宽带(UWB),和啁啾扩频(CSS)。此外,在所提供的表达式上使用不同的度量,以便评估所考虑的PLC脉冲对于提供适当的TDR测量的适用性,即,\textit{reflectograms},在分辨率、脉冲压缩的有效性、失真和范围方面。考虑到欧洲地下低压和美国架空中压配电网的情况下,我们最后进行了比较数值分析所考虑的PLC脉冲在上述指标的频段,包括窄带和宽带PLC,符合监管约束的一个亮点。基于所取得的结果,我们表明,使用UWB脉冲允许在给定的时间间隔内获得更大数量的反射图,而HS-OFDM和CSS脉冲提供更高的反射图质量和更好的分辨率为一个给定的占用频率带宽。此外,我们表明,NB-PLC脉冲是适合于大多数配电网络的情况下,使用BB-PLC留下的情况下,非常精细的分辨率是理想的。
英文摘要:
This work discusses the suitability of typical power line communication (PLC) pulses for fault sensing in power lines via pulse-compression time-domain reflectometry (TDR). For this purpose, we first carefully outline a TDR system operating over a power distribution network, discussing its limitations and ultimately resorting to the pulse compression procedure. Next, we present closed-form expressions for pulses and their autocorrelation functions of typical PLC modulation schemes, namely Hermitian symmetric orthogonal frequency-division multiplexing (HS-OFDM), impulsive ultra-wideband (UWB), and chirp spread spectrum (CSS). Furthermore, different metrics are used on the provided expressions in order to evaluate the suitability of the considered PLC pulses for providing proper TDR measurements, i.e., \textit{reflectograms}, in terms of resolution, effectiveness of the pulse compression, distortion, and range. Considering the scenarios of European underground low-voltage and US overhead medium-voltage power distribution networks, we finally carry out a comparative numerical analysis among the considered PLC pulses in terms of the aforementioned metrics for frequency bands comprising narrowband- and broadband-PLC, with a highlight on compliance to regulatory constraints. Based on the achieved results, we show that the use of UWB pulses allows the obtaining of a larger number of reflectograms in a given time interval, while HS-OFDM and CSS pulses provide higher reflectogram quality and better resolution for a given occupied frequency bandwidth. Also, we show that NB-PLC pulses are suitable for most distribution network scenarios, being the use of BB-PLC left for cases where very fine resolutions are desired.
机构、总结、中文摘要均由AI分析而来,可能存在错误,请以论文正文为准。